1.3 SPECIFICATIONS

1.3 SPECIFICATIONS
1
PHASE CURRENT INPUTS
CT primary:
CT secondary:
Conversion range:
Frequency:
Accuracy:
Current input burden:
FIELD CURRENT INPUTS
CT Primary:
Conversion range:
Accuracy:
EXCITER VOLTAGE INPUTS
Conversion:
Accuracy:
POWER FACTOR
Range:
Time Delay:
Accuracy:
SWITCH INPUTS (MX AND NX)
Type:
Internal interrogation voltage: 85 to 265 V AC (control voltage)
PF ANALOG OUTPUT
Type:
Output:
Accuracy:
Isolation:
CONTROL VOLTAGE
Input:
Power:
Holdup:
RELAY CONTACT
It is recommended that the SPM be powered up at least once per year to prevent deterioration
of electrolytic capacitors in the power supply.
NOTE
1-4
Courtesy of store.ips.us
5 to 2000 A
5 A
0.05 to 6 × CT
50 / 60 Hz
at < 2 × CT: ±0.5% of 2 × CT true RMS
at ≥ 2 × CT: ±1% of 6 × CT true RMS
<1 VA at 5 A
5 to 1000 A
0.05 to 1 × CT
±2%
0 to 350 V DC (prior to VDN)
±1%
0.01 to 1 to –0.01
0.1 to 10 seconds
±5%
Dry contact
Active
0 to 10 V DC max. at RL ≥ 1 KW (min. load)
±10% (0.1 V)
36 V pk
85 to 265 V AC at 48 to 60 Hz
10 VA nominal
100 ms typical at 120 V AC
Specifications are subject to change without notice.
SPM Synchronous Motor Protection and Control

1.3.1 TECHNICAL SPECIFICATIONS

Type:
FAR, TRP: Form A
FCX: Form C
Rated load:
10 A AC continuous: NEMA A300
1 A DC continuous: NEMA R300
Break:
10 A at 250 V AC or 30 V DC
Max. operating voltage:
250 V AC
ENVIRONMENT
Humidity:
0 to 95% non-condensing
Operating Temp.:
–20°C to +70°C
Storage Temp.:
–40°C to +85°C
TYPE TESTS
Dielectric Strength:
Per IEC 255-5 and ANSI/IEEE C37.90
2.0 kV for 1 min. from relays, CTs, VTs
power supply to Safety Ground
Insulation Resistance:
IEC255-5 500 VDC, from relays, CTs, VTs
power supply to Safety Ground
Transients:
ANSI C37.90.1 Oscillatory (2.5kV/1MHz)*
ANSI C37.90.1 Fast Rise (5kV/10ns)*
Ontario Hydro A-28M-82
IEC255-4 Impulse/High Frequency Distur-
bance, Class III Level
Impulse Test:
IEC 255-5 0.5J 5kV
EMI:
C37.90.2 Electromagnetic Interference at
150 MHz and 450 MHz, 10V/m
Static:
IEC801-2 Static Discharge
Vibration:
Sinusoidal Vibration 8.0g for 72 hrs.
* With the use of an isolation transformer. Please contact GE
Multilin technical support for recommended products.
CERTIFICATION
UL:
UL listed for the USA and Canada
PHYSICAL
Shipping Box:
12.50" × 10.50" × 9.75" (L × H × D)
318 mm × 267 mm × 248 mm (L × H × D)
Ship Weight:
14.25 lb. / 6.45 kg