6.4 RECORDS

6.4RECORDS
PATH: ACTUAL VALUES
 EVENT RECORDS
The event records menu shows the contextual data associated with up to the last 1024 events, listed in chronological order
from most recent to oldest. If all 1024 event records have been filled, the oldest record will be removed as a new record is
added. Each event record shows the event identifier/sequence number, cause, and date/time stamp associated with the
event trigger. See the
Only major output operands generate events, not every operand. Elements that assert output per phase, for example, log
operating phase output only without asserting the common three-phase operand event.
PATH: ACTUAL VALUES
 OSCILLOGRAPHY
6
This menu allows the user to view the number of triggers involved and number of oscillography traces available. The
value is calculated to account for the fixed amount of data storage for oscillography. See the Oscillog-
CYCLES PER RECORD
raphy section of chapter 5 for additional details.
A trigger can be forced here at any time by setting "Yes" to the
menu for information on clearing the oscillography records.
CLEAR RECORDS
6-12


RECORDS

EVENT RECORDS

EVENT: XXXX
RESET OP(PUSHBUTTON)
EVENT: 3
MESSAGE
POWER ON
EVENT: 2
MESSAGE
POWER OFF
EVENT: 1
MESSAGE
EVENTS CLEARED
COMMANDS
CLEAR RECORDS


RECORDS

OSCILLOGRAPHY

FORCE TRIGGER?
No
NUMBER OF TRIGGERS:
MESSAGE
0
AVAILABLE RECORDS:
MESSAGE
0
CYCLES PER RECORD:
MESSAGE
0.0
LAST CLEARED DATE:
MESSAGE
2000/07/14
C30 Controller System
menu for clearing event records.
Range: No, Yes
15:40:16
command. Refer to the
FORCE TRIGGER?
6 ACTUAL VALUES
6.4.1 EVENT RECORDS
EVENT 3
DATE: 2000/07/14
EVENT 3
TIME: 14:53:00.03405
Date and Time Stamps
6.4.2 OSCILLOGRAPHY