5 SETTINGS
The dcmA output settings are described below.
DCMA OUTPUT F1 SOURCE: This setting specifies an internal analog value to drive the analog output. Actual values
(FlexAnalog parameters) such as power, current amplitude, voltage amplitude, power factor, etc. can be configured as
sources driving dcmA outputs. Refer to Appendix A for a complete list of FlexAnalog parameters.
DCMA OUTPUT F1 RANGE: This setting allows selection of the output range. Each dcmA channel may be set inde-
pendently to work with different ranges. The three most commonly used output ranges are available.
DCMA OUTPUT F1 MIN VAL: This setting allows setting the minimum limit for the signal that drives the output. This
setting is used to control the mapping between an internal analog value and the output current. The setting is entered
in per-unit values. The base units are defined in the same manner as the FlexElement™ base units.
DCMA OUTPUT F1 MAX VAL: This setting allows setting the maximum limit for the signal that drives the output. This
setting is used to control the mapping between an internal analog value and the output current. The setting is entered
in per-unit values. The base units are defined in the same manner as the FlexElement™ base units.
The
DCMA OUTPUT F1 MIN VAL
the
DCMA OUTPUT F1 SOURCE
NOTE
GE Multilin
I
max
I
min
DRIVING SIGNAL
MIN VAL
Figure 5–52: DCMA OUTPUT CHARACTERISTIC
and
DCMA OUTPUT F1 MAX VAL
is set to FlexAnalog value based on power factor measurement).
C30 Controller System
5.8 TRANSDUCER INPUTS AND OUTPUTS
MAX VAL
842739A1.CDR
settings are ignored for power factor base units (i.e. if
5
5-133