Modbus User Map - GE C30 Instruction Manual

Ur series
Hide thumbs Also See for C30:
Table of Contents

Advertisement

5 SETTINGS
m) ETHERNET SWITCH
PATH: SETTINGS
PRODUCT SETUP
 ETHERNET SWITCH
MESSAGE
MESSAGE
MESSAGE
MESSAGE
These settings appear only if the C30 is ordered with an Ethernet switch module (type 2S or 2T).
The IP address and Modbus TCP port number for the Ethernet switch module are specified in this menu. These settings
are used in advanced network configurations. Please consult the network administrator before making changes to these
settings. The client software (EnerVista UR Setup, for example) is the preferred interface to configure these settings.
The
through
PORT 1 EVENTS
recorder.
PATH: SETTINGS
PRODUCT SETUP
 MODBUS USER MAP
MESSAGE
MESSAGE
MESSAGE
The Modbus user map provides read-only access for up to 256 registers. To obtain a memory map value, enter the desired
address in the
line (this value must be converted from hex to decimal format). The corresponding value is dis-
ADDRESS
played in the
line. A value of "0" in subsequent register
VALUE
lines incremented by "1". An address value of "0" in the initial register means "none" and values of "0" will be dis-
ADDRESS
played for all registers. Different
GE Multilin


COMMUNICATIONS
SWITCH IP ADDRESS:
127.0.0.1
SWITCH MODBUS TCP
PORT NUMBER: 502
PORT 1 EVENTS:
Disabled
PORT 2 EVENTS:
Disabled
PORT 6 EVENTS:
Disabled
settings allow Ethernet switch module events to be logged in the event
PORT 6 EVENTS


MODBUS USER MAP

ADDRESS
1:
VALUE:
0
ADDRESS
2:
VALUE:
0
ADDRESS
3:
VALUE:
0
ADDRESS 256:
VALUE:
0
values can be entered as required in any of the register positions.
ADDRESS
C30 Controller System
ETHERNET SWITCH
Range: standard IP address format
Range: 1 to 65535 in steps of 1
Range: Enabled, Disabled
Range: Enabled, Disabled
Range: Enabled, Disabled
Range: 0 to 65535 in steps of 1
0
Range: 0 to 65535 in steps of 1
0
Range: 0 to 65535 in steps of 1
0
Range: 0 to 65535 in steps of 1
0
lines automatically returns values for the previous
ADDRESS
5.2 PRODUCT SETUP
5.2.5 MODBUS USER MAP
5-37
5

Advertisement

Table of Contents
loading

Table of Contents