GE C30 Instruction Manual page 68

Ur series
Hide thumbs Also See for C30:
Table of Contents

Advertisement

3.2 WIRING
3 HARDWARE
The IRIG-B repeater provides an amplified DC-shift IRIG-B signal to other equipment. By using one IRIG-B serial connec-
tion, several UR-series relays can be synchronized. The IRIG-B repeater has a bypass function to maintain the time signal
even when a relay in the series is powered down.
3
Figure 3–24: IRIG-B REPEATER
Using an amplitude modulated receiver will cause errors up to 1 ms in event time-stamping.
NOTE
3-24
C30 Controller System
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents