TECHNICAL SPECIFICATIONS

3.
3.1

General Specifications

General Information:
Supply Voltage:
Frequency:
Control Supply:
Control Inputs:
Load:
Connection type:
Rated Insulation Voltage:
Rated Impulse Voltage:
Form designation:
This product was tested for compliance with IEC 60947-4-2 for class A equipment.
Start-Stop Parameters:
Starter Current:
Motor Current:
Start/Stop Curve 0
(Standard)
Pump Control Curves (1!,
2!, 3!)
Torque Control Curve (4)
Kick Start Duration:
Starting Voltage:
Initial Current:
Current Limit:
Ramp UP Time:
Ramp DOWN Time:
DUAL Settings Parameters:
Energy Saving:
Slow Speed Torque:
Motor Protection:
Too Many Starts:
Starts Inhibit:
Long Start Time (stall
protection):
Over Current (JAM Fault):
Electronic Overload:
Under Current:
Under Voltage:
Over Voltage:
Refer to sections 2.1 page 8 and 2.2 page 9 for detailed information.
8
Refer to section 5.5.5 page 50 for expanded setting.
9
• Technical Specifications
11
Line to line 230-690V (to be specified) + 10%-15%
45 – 65 Hz (fixed or variable frequency source)
Either 110VAC or 230VAC (to be specified) +10% - 15%
Either 90-230VAC or 24VDC (to be specified)
Three phases, three/six wires, squirrel cage induction motor
Standard 3 wire U, V, W connection, or 6 wire Inside Delta (programmable)
1,000V
4kV
Form 1
ASTAT-XT's rated current according to its nameplate.
Motor Full Load Ampere (Im) 50-125%
2 standard starting and stopping curves
6 field selectable curves preventing over-pressure during start and water hammer
during stop
2 selectable curves preventing over-pressure during start and water hammer during
stop. In addition, these curves may be used for torque control starting of constant
torque applications.
A pulse of 80% Un, for an adj. time 0.1-1 Sec, for starting high friction loads
10-50% Un (5-80%
)
9
100-400% In. A single current control starting curve. It appears when Starting
Voltage is displayed, the up arrow is pressed and Starting Voltage has
reached its max.
100-700% of Motor Current
1-30 Sec (1-90 sec
)
9
9
1-30 Sec (1-90 sec
)
Secondary start stop characteristic for: Starting Voltage, Starting Current, Current
Limit, Ramp UP, Ramp DOWN and Motor Current.
Energy save for lightly loaded motors
Torque while motor is at 1/6 nominal speed
Maximum number of starts, range: Off or 1-10, during a time period 1-60 min.
Time period 1-60 min, when starting is prevented, after too many starts fault
Maximum allowable starting time 1-30 sec. (1-250 Sec
Three trip functions:
At all time - If I > 850% of Starter Current it trips the ASTAT-XT within 1 cycle
(overrides the value of the O/C – JAM Delay setting).
At starting process - If I > 850% of Motor Current it trips the ASTAT-XT after O/C
JAM Delay (see here after)
At run time - If I > O/C – JAM Fault setting of Im it trips the ASTAT-XT after O/C
JAM Delay
Can be set as IEC Class 10, 20 or NEMA Class 10, 20 or 30.
Can be set to operate at all times, disabled or operate during Run only.
Trips when current drops below 20-90% of Motor Current, time delay 1-40 sec.
Optional auto reset after time delay.
Trips when main voltage drops below 120-600V, time delay 1-10 Sec. Optional Auto
Reset.
Trips when main voltage increase above 250-750V, time delay 1-10 sec.
of Starter Current.
8
)
9