GE C30 Instruction Manual page 19

Ur series
Hide thumbs Also See for C30:
Table of Contents

Advertisement

1 GETTING STARTED
3.
Click the Quick Connect button to open the Quick Connect dialog box.
4.
Select the Serial interface and the correct COM Port, then click Connect.
5.
The EnerVista UR Setup software will create a site named "Quick Connect" with a corresponding device also named
"Quick Connect" and display them on the upper-left corner of the screen. Expand the sections to view data directly
from the C30 device.
Each time the EnerVista UR Setup software is initialized, click the Quick Connect button to establish direct communica-
tions to the C30. This ensures that configuration of the EnerVista UR Setup software matches the C30 model number.
b) USING QUICK CONNECT VIA THE REAR ETHERNET PORTS
To use the Quick Connect feature to access the C30 from a computer through Ethernet, first assign an IP address to the
relay from the front panel keyboard.
1.
Press the MENU key until the SETTINGS menu is displayed.
2.
Navigate to the
SETTINGS
3.
Enter an IP address of "1.1.1.1" and select the ENTER key to save the value.
4.
In the same menu, select the
5.
Enter a subnet IP address of "255.0.0.0" and press the ENTER key to save the value.
Next, use an Ethernet cross-over cable to connect the computer to the rear Ethernet port. The pinout for an Ethernet cross-
over cable is shown below.
3 4 5 6
2
7
1
8
Now, assign the computer an IP address compatible with the relay's IP address.
GE Multilin

PRODUCT SETUP
COMMUNICATIONS
setting.
SUBNET IP MASK
END 1
Pin
Wire color
Diagram
1
White/orange
2
Orange
3
White/green
4
Blue
5
White/blue
6
Green
7
White/brown
8
Brown
Figure 1–6: ETHERNET CROSS-OVER CABLE PIN LAYOUT
C30 Controller System
1.3 ENERVISTA UR SETUP SOFTWARE

NETWORK
IP ADDRESS
END 2
Pin
Wire color
Diagram
1
White/green
2
Green
3
White/orange
4
Blue
5
White/blue
6
Orange
7
White/brown
8
Brown
842799A1.CDR
1
setting.
1-11