READ:IO:IN16? <module_name>
Acquires the condition of all input channels of an I/O module. Up to sixteen input
channels (like on module R&S OSP-B103) can be queried. The returned result is an
integer value that represents the condition of all input channels of the module. This
integer value is in the range of 0 (all channel are logical 0-LOW) to 65535 (all channel
are logical 1-HIGH).
'<module_name>'
Example
Characteristics
Operating Manual 1505.3896.12 - 14
Represents the ID of a I/O module within an R&S OSP
instrument.
For more information on naming conventions and how a module
ID is built up, please refer to
READ:IO:IN16? F01A13
Response: 4
16-bit binary equivalent of this value: 0000 0000 0000 0100.
Input channel 3 (one-based) of the I/O module at position A13 in
R&S OSP instrument with ID F01 is in condition HIGH. All other
available channels are in condition LOW.
Firmware version V1.0
Device-specific. Query only.
Remote Command Reference
chapter
7.2, Naming Conventions.