READ:IO:IN4? <module_name>
Acquires the condition of the four I/O input channels of module R&S OSP-B104. The
returned result is an integer value that represents the condition of all input channels of
the module. This integer value is in the range of 0 (all channel are logical 0-LOW) to 15
(all channel are logical 1-HIGH).
'<module_name>'
Example
Characteristics
READ:IO:IN6? <module_name>
Acquires the physical condition of the six relays located on an R&S OSP-B106
module. There are three relays that provide N connectors and three relays that provide
BNC connectors at the front of the module R&S OSP-B106. At the moment it is only
possible to acquire the physical condition of the BNC relays which are numbered 4, 5
and 6.
The returned result is an integer value that is equivalent to a six bit binary value
whereas bit number 3, 4 and 5 represents the condition of the BNC relays numbered
4, 5 and 6. A closed relay is indicated by a bit value of 1, an open relay is indicated by
a bit value of 0.
'<module_name>'
Example
Characteristics
Operating Manual 1505.3896.12 - 14
Represents the ID of an R&S OSP-B104 module within an
R&S OSP instrument.
For more information on naming conventions and how a module
ID is built up, please refer to
READ:IO:IN4? F01A13
Response: 4
4-bit binary equivalent of this value: 0100. Input channel 3 (one-
based) of the R&S OSP-B104 module at position A13 in
R&S OSP instrument with ID F01 is in condition HIGH. All other
available channels are in condition LOW.
Firmware version V1.1
Device-specific. Query only.
Represents the ID of an R&S OSP-B106 module within an
R&S OSP instrument.
For more information on naming conventions and how a module
ID is built up, please refer to
READ:IO:IN6? F02A11
Response: 8
6-bit binary equivalent of this value: 001000. Relay 4 (one-
based) of the R&S OSP-B106 module at position A11 in
R&S OSP instrument with ID F02 is in 'closed'-condition. All
other relays are in 'open'-condition.
Firmware version V1.3
Device-specific. Query only.
Remote Command Reference
chapter
7.2, Naming Conventions.
chapter
7.2, Naming Conventions.
160