Daikin DCM601A51 Technical Data Manual page 72

Air conditioners intelligent touch manager
Hide thumbs Also See for DCM601A51:
Table of Contents

Advertisement

Adaptor
5. Temperature setting input
Temperature setting corresponds to resistance values in the range of 0 to 135Ω.
Their relationship is as shown below.
Relation between the setting temperature and the resistance are as follows.
Setting
temperature (°C)
Resistance (Ω)
Note:
The value of resistance includes the resistance of wiring.
The setting temperature is limited within the setting range of indoor unit. If you set the temperature outside of the
range by the adaptor, it controls at the nearest setting range.
6. Setting of control mode selector switch (RS1)
CONTROL
MODE
Position
RS1
1
0
Input Ignored
1
Remote Control Rejection
2
Central Priority
Remote controller Acceptable/
3
Rejection
Remote controller acceptance /
4
rejection, OFF
Position
5
Remote Control Rejection
6
Last command Priority
68
KRP4A54
16
17
18
19
0.0
5.0
13.8
22.4
31.0
~
~
~
~
3.4
11.6
20.0
28.4
36.4
Operation
Function
Operation
Function
1.2 Wiring Adaptor for Electrical Appendices (2) <KRP4AA51 / KRP4AA52 / KRP4AA53 / KRP4A54>
20
21
22
23
24
39.4
48.2
56.6
65.2
~
~
~
~
~
44.8
52.8
61.2
69.4
Input A close
or not of
From Remote
indoor
controller
unit
ON
Rejection
ON
Acceptable
Only Stop
ON
acceptable
Permit
Acceptable
Input A close/open
(pulse input)
or not of
From Remote controller
indoor
unit
ON /
Rejection
OFF
ON /
Acceptable
OFF
C: 1PA59890F
25
26
27
28
29
73.8
82.4
91.0
99.4
108.6
~
~
~
~
~
77.8
85.8
94.0
102.2
110.4
Input A open
Operation
or not of
From Remote
indoor
controller
unit
OFF
Rejection
Constant Input B close
( Constant input) (Input A is ignored)
Operation or not of
indoor unit
Forced OFF at close
ED721208
30
31
32
117.2
125.8
134.2
~
~
~
119.2
127.4
140.0
Input B close
(Input A is ignored)
Operation
From
or not of
Remote
indoor
controller
unit
Forced
Rejection
OFF
From Remote
controller
Rejection

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dcm601a52Dcm601a53

Table of Contents