The figure below shows the PC board built in this equipment.
Transmission error monitor
(LED10: Red)
When the transmission is
abnormal, the lamp lights up,
disabling remote control.
(The lamp goes out in the
normal condition.)
Micro-computer OK monitor
(LED-A: Green)
When the micro-computer is in
normal operation, the lamp flickers.
Abnormal output cutoff / hold
switch (DS5)
This switch makes it possible to
select whether the operation
output is interrupted or held
when an abnormality occurred
in the connected equipment.
Quantity change shortcircuit
pin (TP1)
Shortcircuit during control
quantity setting
Start error masks witch
(DS6-1)
It is possible to select whether
the error at startup is masked
for 10 or 30 seconds.
Error detecting switch
(DS6-2)
It is possible to select whether
the equipment connection error
is a non-latch or latch error.
2.3 Dio Unit <DEC102A51>
Power supply terminal
block (L, N)
For the power supply,
use 1 ~ 200 - 240V.
Switch for selecting the number
of facility equipment connected
(DS3)
Set the switch according to the number
of facility equipment connections.
Transformer connecting
connector (CN1/CN2)
The power transformer
connector is connected.
X1A
AC200V
~240V
RED
INPUT
L
Aiarm
Monitor
(RED)
N
Operation
Monitor
(GRN)
X1M
LED10
HAP
RED
HAP
GRN
TNa1
TNb1
TNa2
TNb2
TNa3
TNc1
TNc2
TNc3
X4M
CD
D1
D2
Terminal block for control
output (Terminal size: M3.5)
The start / stop signal is outputted
to the equipment to be connected.
DIII-NET Address No. setting
switch (RS1/DS1)
Set DIII-NET Address No.
X2A
YE
1
2
3
4
H10P
Group No. Set
DS1 High
H1P H2P
H3P
H4P
H9P
H10P
H11P
H12P
DS3
1
2
3
4
TP1
DS5
1
2
3
4
TNb3
TNa4
TNb4
Contact switch
Con. Ins.
TNc4
CA
A1
A2
A3
A4
D3
D4
CM
M1
M2
M3
M4
Terminal block for monitor
input (Terminal size: M3.5)
The facility equipment status
is monitored.
Output selector switch (SS1)
This switch makes it possible to select
continuous 1 output or instantaneous 2 output.
Terminal block for transmission
(F1/F2) (Terminal size: M3)
Connect this unit to the terminals F1, F2
of the centralized control equipment.
Abnormal input detecting switch
(DS2)
Whether the connected equipment
"error" is detected with contact input
"Open" or "Closed" can be selected.
Momentary stop auto switch (DS4-1)
X2M
This switch makes it possible to
F1
select whether the system should
be reset to the state before power
F2
failure or not when the power
failure was recovered.
RS1 Low
0
Transmission error switch (DS4-2)
This switch makes it possible to
DS2
5
6
7
8
select whether the control output
ON
state is maintained or not when
the transmission is abnormal.
DS4
5
6
7
8
ON
Later push priority switch (DS4-3)
This switch makes it possible to
DS6
ON
select the absence or presence
1
2 3
4
of later push priority switch.
SS1
Start / Stop error switch (DS4-4)
Switching of whether or not error
X3M
detection for start / stop operation
from i-Manager is done is performed.
Forced stop switch (DS6-4)
This switch makes it possible to
select whether the forced stop
signal should be followed or
neglected.
Monitor input switch
(DS6-3)
Whether or not the abnormal condition
of facility equipment during stop is
recognized can be selected.
Adaptor
4
125