Adaptor
2. Initial setting
DEC101A51 Switch Settings
Abnormal input detection Open/Close
DS2
(Concentrated address +4 to 7)
Abnormal input detection Open/Close
DS3
(Concentrated address +0 to 3)
Buzzer output ON/OFF (Concentrated
DS4
address +4 to 7)
Buzzer output ON/OFF (Concentrated
DS5
address +0 to 3)
DS6-1
Startup failure
DS6-2
Failure detection
DS6-3
Monitor input
Note:
All are set to "OFF" upon shipment from factory.
Set the top address of this equipment with the DIII-NET setting switch (DS1/RS1).
Using the DIII-NET setting switch (DS1), set the range of Address No. that is set in this equipment.
Address Nos. 1-00 to 1-15 are factory controlled before shipment.
Control range DS1
Control range DS1
setting
Set Address No. (low order) with the centralized address setting switch (RS1).
Referring to the table below, set the address number low order.
(Address Nos. are 1-00, 1-01, --- 1-15, 2-00, --- 4-15.)
RS1 Switch Setting Table
Position
Address No.
<when a product is
discharged from the factory>
118
Name
1-00 ~ 1-15
(high order)
ON
(Address range)
When a product is
discharged from the factory
0
1
2
3
4
5
6
7
00
01
02
03
04
05
06
07
<Example>
When Address No.
is set to 1-08
DS1
ON
High
order : 1
Operation
Abnormal input detection method
Open: Close (Normal) → Open (Abnormal)
Close: Open (Normal) → Close (Abnormal)
ON/OFF switching of buzzer output of
buzzer unit upon detection of failure.
Masking time after detecting operation
input.
Recovery method upon detection of
failure.
Detection of failure under halting status.
2-00 ~ 2-15
3-00 ~ 3-15
ON
ON
This indicates the switch knob.
8
9
A
B
C
D
E
F
08
09
10
11
12
13
14
15
Address No. indicates the
following portion in this case.
RS2
1-08
High
Low
8
order
order
Low
order : 8
OFF
Open
Open
ON
ON
10 seconds
30 seconds
Automatic
reset
Yes
4-00 ~ 4-15
ON
(low order)
In this case, it follows
that this equipment uses
Address Nos.
1-08 to 1-15.
(8 numbers max.)
2.2 Di Unit <DEC101A51>
ED721208
ON
Close
Close
OFF
OFF
Retained
No