Daikin DCM601A51 Technical Data Manual page 181

Air conditioners intelligent touch manager
Hide thumbs Also See for DCM601A51:
Table of Contents

Advertisement

ED721208
1.4
1.4.1
1.4.2
Required installa-
tion space
10
The table below shows the status of the CPU ALIVE/ALARM LED when the iTM plus
adaptor is operating normally or failed.
NOTE
[LED status and operation table]
Operating condition
Hardware failure
Address failure
plus ADP IF communication failure
Be sure to install the iTM plus adaptor in a place that meets the conditions described in
1.4.1 through 1.4.3.
described below:
Installation place: Indoor, inside control enclosure (which must be lockable or designed
Mounting direction: Vertical only
Required space
To install the iTM plus adaptor, the following space is required. Also note the following:
Make sure that there is a minimum clearance of 20 mm between each unit and wiring
ducts.
When installing two or more units side by side, they can be arranged without clearance
in the horizontal direction.
A
160mm
A
A
Wiring duct
Installation Manual 3P291714-3
DCM601A52 iTM plus adaptor
CPU ALIVE
ALARM
Blink
Off
Off
On
On
On
On
Blink
40mm
20mm
20mm
40mm
Installation Manual
5
20mm
English
177