Daikin DCM601A51 Technical Data Manual page 239

Air conditioners intelligent touch manager
Hide thumbs Also See for DCM601A51:
Table of Contents

Advertisement

ED721208
(44)
Sets up the upper limit and monitoring status for upper limit error monitoring.
For the upper limit, touch the Modify button and enter it in the Numerical Input dialog that
appears.
For the monitoring status, select from Disable, Monitoring, and Monitor + History from the combo
box.
(45)
Select the analog value type from Temperature and Other.
(46)
Select the unit type of External Ai either "Thermistor" or "Other". The unit type cannot be
512.0 (or –890 and 954 in Fahrenheit), respectively, which cannot be changed.
(47)
Sets up the physical quantities corresponding to the minimum and maximum analog value input
signals.
Touch the Modify button and enter the value in the Numerical Input dialog that appears.
(48)
Sets up the Target Point and Target analog value for the Internal Ai.
Touch the Ref.. button and select the Target Point and Target analog value to set from the Analog
Point Selection screen that appears (see page 32).
Upper Limit
Analog Type radio button
Unit Type radio button
Minimum Value / Maximum Value
Reference settings
Commissioning Manual EM11A021
DCM601A51 intelligent Touch Manager
(45).
(47)
Commissioning Manual
to –512.0 and
30
235
6