Daikin DCM601A51 Technical Data Manual page 131

Air conditioners intelligent touch manager
Hide thumbs Also See for DCM601A51:
Table of Contents

Advertisement

ED721208
2.3.3 Installation
(Installation Place)
Install the unit indoors where it is not exposed to water and dust or dirt.
Install the unit where both temperature and humidity do not become high.
(Operating (available) temperature: -10 ~ +40˚C)
(Operating (available) humidity: 10 ~ 85%)
Connect the wiring to be connected in the field from the lower surface side.
It is, therefore, necessary to make arrangements so as not to attach other equipment within 80mm from the
lower surface of this equipment.
Install this equipment in a place in which only the authorized personnel can touch it.
(Installation Direction)
Install this equipment vertically to the floor surface. It should be noted that if it is installed in the horizontal
direction, a malfunction or failure may result.
(Installation Method)
Install in container box or in panel.
Ensure that this equipment is installed with 4 screws (screw size M4 min.).
2.3 Dio Unit <DEC102A51>
UP
(198)
70
70
DEC102A51
Front panel screw
Mounting hole
Mounting hole
Adaptor
Unit (mm)
127
4

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dcm601a52Dcm601a53