Mask time for abnormal input after operation command
DS6-1
DS6-2
DS6-3
DS6-4
SS1
TNa
DS3
130
Condition
Range of address No.
A1 - AM
Power failure, then after power recovery
Communication abnormal
Last command priority or C/C only
Operation commands from C/C reach to C/D , but no
operation.
Of abnormal in C/D,
from C/C
After error of C/D is recovered
Abnormal input + stop state of C/D
Forced stop command from C/C
Continuous output "Con" / Instantaneous output "Ins"
"a" contact or "b" contact for CD- D1~4
Number of C/D
C/C : Centralized control equipment
C/D : Connectable Devices or Facility equipment
Factory preset before shipment
1-00, 01, 02, 03
Abnormal in the open condition
Stop
Stop
Last command priority
No abnormality signal to C/C
CD- D1~4 is "turned off".
10 seconds
Automatic reset
Error display on C/C
C/D stop
Continuous output
"a" contact
4
"a" contact: make-contact, "b" contact: break-contact