ED721208
Cautions:
1. Never use a 3 or more core of cord or cable.
2. The size of wire should be 0.75~1.25mm².
3. Never bundle the cable or cord of transmission line.
4. Be sure to keep the transmission wiring distant from power wiring as shown below to prevent electrical noise.
220V or less
Note:
1.
1 .....VRV system, SkyAir series and other air-conditioner.
2.
2 .....VRV system or other Daikin air-conditioner produces less electrical noise, so that the distance of 50mm or
more is sufficient.
3. For control wiring, never use the shield wire together with other sheathed vinyl cord in the same system, which may
cause the malfunction in transmission.
[Example]
2.7 Wiring Specifications of DIII-NET
Capacity of power wiring
10A or less
50A or less
100A or less
100A or more
Distance between Power wiring and control wiring
Daikin air-conditioner ( 1)
50mm or more ( 2)
Fundamental of DIII-NET
Other air-conditioners
300mm or more
500mm or more
1000mm or more
1500mm or more
25