Select whether to block the control signal when an error is detected from Enable and Disable.
(33)
(34)
Select the type of output contact from A type and B type.
Pulse Tab
Sets up the pulse value.
Displayed items vary depending on the management point type.
(35)
Sets up the pulse value.
Touch the Modify button and enter the value in the Numerical Input dialog that appears.
You can enter a value in the –1 to 999999999 range, in increments of 1.
(36)
Sets up the pulse constant.
Touch the Modify button and enter the value in the Numerical Input dialog that appears.
You can enter a value in the 1 to 999999 range, in increments of 1.
(37)
Sets up the unit.
Touch the Modify button and enter the value in the Text Input dialog that appears.
The number of characters you can enter is 0 to 8, irrespective of single or double byte.
27
232
Post-Priority radio button
Error output holding radio button
Start-Stop Error radio button
Output Contact A/B radio button
(35)
(36)
(37)
(38)
<Pi>
Pulse Amount
Pulse Step
Unit Label
Commissioning Manual EM11A021
DCM601A51 intelligent Touch Manager
(37)
(38)
(39)
(40)
<Internal Pi>