Daikin DCM601A51 Technical Data Manual page 235

Air conditioners intelligent touch manager
Hide thumbs Also See for DCM601A51:
Table of Contents

Advertisement

ED721208
Dio Tab
Sets up the Dio.
Displayed items vary depending on the management point type.
(26)
Select the Di Point Type from A type and B type.
(27)
Select the Di operation mode from Normal and Equipment error input.
(28)
Select an Error Mask Time after operation input from 10 and 30 seconds.
Start up error occurs if the external Di or external Dio cannot start even after the time set up here
elapses from the moment the Start signal has been received.
(29)
Select whether to carry out error detection when the external Di or external Dio is off from Enable
and Disable.
(30)
Select the error input detection from A type and B type.
(26)
(27)
<Di>
(26)
(31)
(32)
(28)
Point Type radio button
Operation Mode radio button
Error input masking time after start signal radio button
Monitor Input radio button
Error input type radio button
Commissioning Manual EM11A021
DCM601A51 intelligent Touch Manager
<External Di>
(29)
(30)
<External Dio>
Commissioning Manual
(26)
(28)
(29)
(30)
(33)
(34)
26
6
231