ED721208
1.2.4 Electric Wiring Work and Initial Setting
1. Wiring
2. Depending on whether [voltage input] or [non voltage input], connect the wiring as shown below.
Input/Output for External Control
3. Depending on whether [voltage input] or [non voltage input], connect the wiring as shown below.
Input with Voltage.
Set the Voltage/Non voltage changeover switch (SS1) to VOLT.
Input with No Voltage.
Set the Voltage/Non voltage changeover switch (SS1) to NON VOLT.
4. Display Signal Retrieval (Output)
The normal operation output terminals (W1, W2) and error output terminals (W3, W4) are non-voltage output contacts.
(Permissive current is 10mA~3A per contact.)
Output is as given below.
Output
System
Group control
1.2 Wiring Adaptor for Electrical Appendices (2) <KRP4AA51 / KRP4AA52 / KRP4AA53 / KRP4A54>
Both Ry1 and Ry2 is OFF.
OFF
Only Ry1 is ON.
At least one unit is stopped due to error
All normal operation
or transmission error between the
adaptor and the indoor unit.
Adaptor
Only Ry2 is ON.
C: 1PA59890F