The figure below shows the printed circuit board built in this equipment.
Power supply terminal
block (L, N)
For the power supply,
use 1
Transmission error monitor
(LED10: Red)
When the transmission is
abnormal, the lamp lights up,
disabling remote control.
(The lamp goes out in the
normal condition.)
Micro-computer OK monitor
(LED-A: Green)
When the micro-computer is in
normal operation, the lamp flickers.
Quantity change shortcircuit pin
(TP1)
Shortcircuit during control
quantity setting
2. Specifications
Input contacts
Installation method
Power supply
Rating
Applied Standard
Environment for use
Environment for storage
114
Transformer connecting connector
(CN1/CN2)
The power transformer connector
~
200 - 240V.
is connected.
X1A
AC200V
RED
~ 240V
L
INPUT
Aiarm
N
Monitor
(RED)
X1M
Operation
Monitor
(GRN)
H17P
RED
HAP
GRN
TP1
CA
CM
Terminal block for monitor input
(Terminal size: M3.5)
The facility equipment status
is monitored.
Outdoor air temperature
Ambient humidity
Outdoor air temperature
Ambient humidity
DIII-NET Address No. setting switch
(RS1/DS1)
Set DIII-NET Address No.
X2A
YE
1
2
3
4
5
6
7
8
Group No. Set
DS1 High
H6P
H7P
H8P
H1P
H2P
H3P
H4P
H5P
H9P
H10P
H11P
H12P
H13P
H14P
H15P
H16P
DS3
1 2 3 4
DS5
1 2 3 4
A1
A2
A3
A4
A5
A6
A7
A8
M1
M2
M3
M4
M5 M6
M7
M8
Di board
16 points.
8 pairs based on a pair of On/Off input and abnormality input
* Contact information(On/Off, Abnormality ) is transmitted to
intelligent Touch Controller / intelligent Manager III through DIII-
Net communication.
Indoor installation
To be supplied from outside
AC200-240V, 50/60Hz
Safety standard: IEC730, EMC standard: CISPR22-A (EMI),
CISPR24 (EMS)
–15 to 60 °C
95%RH or less (no condensation)
–20 to 60 °C
95%RH or less (no condensation)
Terminal block for transmission (F1/F2)
(Terminal size: M3)
Connect this unit to the terminals F1, F2
of the centralized control equipment.
Abnormal input detecting switch
(DS2/DS3)
Whether the connected equipment "error"
is detected with contact input "Open" or
"Closed" can be selected.
X2M
F1
Switch for selecting the number
F2
of facility equipment connected
(DS4/DS5)
RS1 Low
0
Set the switch according to the number
of facility equipment connections.
DS2
5 6 7 8
ON
Start error mask switch
DS4
5 6 7 8
(DS6-1)
ON
It is possible to select whether the
error at startup is masked for
ON
10 or 30 seconds.
1 2 3 4
DS6
Error detecting switch
X3M
(DS6-2)
It is possible to select whether the
equipment connection error is a
non-latch or latch error.
Monitor input switch
(DS6-3)
Whether or not the abnormal condition
of facility equipment during stop is
recognized can be selected.