Control Circuit Terminal Functions

The functions of the control circuit terminals are shown in Table 2.10. Use the appropriate terminals for the correct
purposes.
No.
Type
S1
Forward run/stop command
S2
Reverse run/stop command
S3
Multi-function input 1
S4
Multi-function input 2
S5
Multi-function input 3
S6
Multi-function input 4
S7
Multi-function input 5
Digital
input
signals
S8
Multi-function input 6
S9
Multi-function input 7
S10
Multi-function input 8
S11
Multi-function input 9
S12
Multi-function input 10
SC
Sequence input common
Table 2.10 Control Circuit Terminals
Signal Name
Forward run when CLOSED; stopped when OPEN.
Reverse run when CLOSED; stopped when OPEN.
Factory setting: External fault when
*1
*1
Factory setting: Fault reset when CLOSED.
Factory setting: Multi-speed speed
*1
reference 1 effective when CLOSED.
Factory setting: Multi-speed speed
*1
reference 2 effective when CLOSED.
Factory setting: Jog frequency selected when
*1
Factory setting: External baseblock when
*1
Factory setting: Multi-speed speed
*1
reference 3 effective when CLOSED.
Factory setting: Multi-speed speed
*1
reference 4 effective when CLOSED.
Factory setting: Accel/decel time selected
*1
Factory setting: Emergency stop
*1
(NO contact) when CLOSED.
Wiring Control Circuit Terminals
Function
CLOSED.
CLOSED.
CLOSED.
when CLOSED.
-
Signal Level
Multi-
function
digital
24 Vdc, 8 mA
inputs.
Photocoupler
Functions
isolation
set by
H1-01 to
H1-10
23
2-