YASKAWA CIMR-G7U Technical Manual page 229

Hide thumbs Also See for CIMR-G7U:
Table of Contents

Advertisement

The operation after stopping depends on the setting of b1-05 when flux vector control is selected (A1-02 = 3).
Run command OFF
Frequency reference
via analog input
0
b1-05=0
(frequency reference)
Injection brake
time at start
b2-03
Baseblock
b1-05=1
Injection brake
(Coast)
time at start
Baseblock
b1-05=2
(Run on E1-09)
Injection brake
time at start
Baseblock
b2-03
b1-05=3
Injection brake
(Zero speed)
time at start
Baseblock
b2-03
Fig 6.12 Deceleration to Stop (for Flux Vector Control)
Coast to Stop
If the stop command is input (i.e., the run command is turned OFF) when b1-03 is set to 1, the Drive output
voltage is interrupted. The motor coasts to a stop at the deceleration rate that counterbalances damage to the
machine and inertia including the load.
Run command
Output frequency
After the stop command is input, run commands are ignored until the Minimum Baseblock Time (L2-03) has
elapsed.
INFO
ON
Zero speed
control
b2-03
ON
Inverter output freqeuencty interrupted.
Fig 6.13 Coast to Stop
OFF
E1-09
Run command turns OFF
and zero speed control start
when motor speed drops to b2-01.
Zero speed
control
Baseblock
b2-04
Frequency reference drops to less
than E1-09 and zero speed control
starts when motor speed drops to
b2-01.
Baseblock
b2-04
Run command turns OFF
and zero speed control start
when motor speed drops to b2-01.
Zero speed control
Baseblock
b2-04
Run command turns OFF
and zero speed control start
when motor speed drops to b2-01.
Zero speed control
Baseblock
b2-04
OFF
Stopping Methods
11
6-