YASKAWA CIMR-G7U Technical Manual page 396

Hide thumbs Also See for CIMR-G7U:
Table of Contents

Advertisement

Display
OPE10
V/f data setting error
V/f Ptrn Set-
ting
OPE11
Carr Freq/
Parameter setting error
On-Delay
ERR
EEPROM
EEPROM write error
R/W Err
-14
7
Table 7.3 Operation Error Displays and Incorrect Settings (Continued)
Meaning
Parameters E1-04, E1-06, E1-07, and E1-09 do not satisfy the following conditions:
• E1-04 (FMAX)  E1-06 (FA) > E1-07 (FB)  E1-09 (FMIN)
• E3-02 (FMAX)  E3-04 (FA) > E3-05 (FB)  E3-07 (FMIN)
One of the following parameter setting errors exists.
• C6-05 (Carrier Frequency Gain) > 6, the Carrier Frequency Lower Limit (C6-04)
> the Carrier Frequency Gain(C6-05)
• Upper/lower limit error in C6-03 to 05.
• C6-01 is 0 and C6-02 is 2 to E.
• C6-01 is 1 and C6-02 is 7 to E.
A verification error occurred when writing EEPROM.
• Try turning the power supply off and on again.
• Try setting the parameters again.
Incorrect settings