YASKAWA CIMR-G7U Technical Manual page 332

Hide thumbs Also See for CIMR-G7U:
Table of Contents

Advertisement

 E1-04 Maximum Output Frequency
Setting Range:
Factory Default: 60.0Hz
 E1-05 Maximum Output Voltage
Setting Range:
Factory Defaults: 230.0V (200-240V Models)
 E1-06 Base Frequency
Setting Range:
Factory Default: 60.0Hz
 E1-07 Mid Output Frequency A
Setting Range:
Factory Default: 3.0Hz
 E1-08 Mid Output Voltage A
Setting Range:
Factory Defaults: 12.6V (200-240V Models)
 E1-09 Minimum Output Frequency
Setting Range:
Factory Default: 0.5Hz
 E1-10 Minimum Output Voltage
Setting Range:
Factory Defaults: 2.3V (200-240V Models)
 E1-11 Mid Output Frequency B
Setting Range:
Factory Default: 0.0Hz
 E1-12 Mid Output Voltage B
E1-13 Base Voltage
Setting Range:
Factory Defaults: 0.0V (200-240V Models)
To set up a custom V/f pattern, program the points shown in the diagram below using parameters E1-04 through
E1-13. Be sure that the following condition is true:: E1-09  E1-07  E1-06  E1-11 E1-04
-114
6
0.0 to 400.0Hz
0.0 to 255.0V (200-240V Models)
0.0 to 510.0V (380-480V Models)
480.0V (380-480V Models)
0.0 to 400.0Hz
0.0 to 400.0Hz
0.0 to 255.0V (200-240V Models)
0.0 to 510.0V (380-480V Models)
25.2V (380-480V Models)
0.0 to 400.0Hz
0.0 to 255.0V (200-240V Models)
0.0 to 510.0V (380-480V Models)
4.6V (380-480V Models)
0.0 to 400.0Hz
0.0 to 255.0V (200-240V Models)
0.0 to 510.0V (380-480V Models)
0.0V (380-480V Models)