Frequency
If the frequency reference loss
Reference
function is enabled (L4-05=1)
at
and frequency reference is lost,
Reference
the Drive will run at a reduced
L4-06
Loss
frequency reference
determined by the following
Fref at
formula: Fref = Fref at time of
Floss
loss * L4-06.
Torque
Selects the control method for
Limit
the torque limit during
Control
acceleration and deceleration.
Method
0: Proportional Control
During
L4-07
(integral control at fixed
Accel/
speeds)
Decel
1: Normal integral control, no
Torque
need to change settings.
Limit Sel
Fault Restart: L5
User parameters for restarting faults are shown in the following table.
Name
Parameter
Number
Display
Number of
Sets the counter for the number
Auto
of times the Drive will perform
Restart
an automatic restart on the
Attempts
following faults: GF, LF, OC,
OV, PF, PUF, RH, RR, OL1,
OL2, OL3, OL4, UV1. Auto
restart will check to see if the
fault has cleared every 5ms.
L5-01
When no fault is present, the
Drive will attempt an auto
Num of
restart. If the Drive faults after
Restarts
an auto restart attempt, the
counter is incremented. When
the Drive operates without fault
for 10 minutes, the counter will
reset to the value set in L5-01.
Auto
Determines if the fault contact
Restart
activates during an automatic
Operation
restart attempt.
Selection
0: No Fault Relay - fault
contact will not activate
L5-02
during an automatic restart
attempt.
1: Fault Relay Active - fault
Restart Sel
contact will activate during
an automatic restart
attempt.
Setting
Factory
Description
Range
Setting
0.0
to
100.0%
0 to 1
Setting
Factory
Description
Range
Setting
0 to 10
0 to 1
Control Methods
Change
Open
V/f
during
Loop
V/f
with
Operation
Vector
PG
1
80%
No
A
A
A
0
No
No
No
A
Control Methods
Change
Open
V/f
during
Loop
V/f
with
Operation
Vector
PG
1
0
No
A
A
A
0
No
A
A
A
User Parameter Tables
Open
MODBUS
Flux
Loop
Register
Vector
Vector
2
A
A
4C2H
No
No
4C9H
Open
MODBUS
Flux
Loop
Register
Vector
Vector
2
A
A
49EH
A
A
49FH
67
5-

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents