Option Parameters: F

The following settings are made with the option parameters (F parameters): Settings for Option Cards.
PG Option Setup: F1
User parameters for the PG Speed Control Card are shown in the following table.
Name
Parameter
Number
Display
PG Parameter Sets the number of pulses per
F1-01
PG Pulses/
Rev
Operation
Selection at
PG Open
Circuit
(PGO)
F1-02
PG Fdbk
Loss Sel
Operation
Selection at
Overspeed
(OS)
F1-03
PG
Overspeed
Sel
Operation
Selection at
Deviation
F1-04
PG
Deviation Sel
Setting
Description
Range
0
revolution (PPM) of the
to
encoder (pulse generator).
60000
Sets stopping method when a
PG open circuit fault (PGO)
occurs. See parameter F1-14.
0: Ramp to stop - Decelerate
to stop using the active
deceleration time.
0 to 3
1: Coast to stop
2: Fast - Stop - Decelerate to
stop using the deceleration
time in C1-09.
3: Alarm Only - Drive
continues operation.
Sets the stopping method
when an overspeed (OS)
fault occurs. See F1-08 and
F1-09.
0: Ramp to stop - Decelerate
to stop using the active
deceleration time.
0 to 3
1: Coast to stop
2: Fast - Stop - Decelerate to
stop using the deceleration
time in C1-09.
3: Alarm Only - Drive
continues operation.
Sets the stopping method
when a speed deviation
(DEV) fault occurs.
See F1-10 and F1-11.
0: Ramp to stop - Decelerate
to stop using the active
deceleration time.
0 to 3
1: Coast to stop
2: Fast - Stop - Decelerate to
stop using the deceleration
time in C1-09.
3: Alarm Only - Drive
continues operation.
Control Methods
Change
Open
Factory
V/f
during
Loop
Setting
V/f
with
Operation
Vector
PG
1
1024
No
No
Q
No
1
No
No
A
No
1
No
No
A
No
3
No
No
A
No
User Parameter Tables
Open
MODBUS
Flux
Loop
Register
Vector
Vector
2
Q
No
380H
A
No
381H
A
A
382H
A
A
383H
41
5-