YASKAWA CIMR-G7U Technical Manual page 439

Hide thumbs Also See for CIMR-G7U:
Table of Contents

Advertisement

EMC Directive
Varispeed G7-Series Drives satisfy testing for conformance to the EMC Directive under the conditions
described in European Standard EN61800-3.
Installation Method
In order to ensure that the machinery or installation incorporating the Drive conforms to the EMC Directive,
perform installation according to the method below.
Install a noise filter that conforms to European Standards on the input side. (Refer to Table 10.3 EMC
Noise Filters).
Use a shielded line or metal piping for wiring between the Drive and Motor. Make the wiring as short as
possible.
To suppress harmonics, install a DC reactor in CIMR-G7U20P4, 20P7, 40P4, and 40P7 models. (Refer to
Table 10.4 DC Reactors for Suppressing Harmonics.)
Metallic plate
Remove the paint on the ground side.
Fig 10.6 Installation Method for Filter and Drive (CIMR-G7U20P4 to 2018, 40P4 to 4018)
L1 L2L3PE
Remove the paint on the ground side.
Inputs
Drive
Filter
Outputs
L1L2L3 T1T2T3
Wiring length:
40 cm max.
Conformance to UL and CE Markings
Wiring length: 20 m max.
IM
15
10-

Hide quick links: