Lenovo x3650 M5 Installation And Service Manual page 429

Hide thumbs Also See for x3650 M5:
Table of Contents

Advertisement

Alert Category
Critical - Temperature
SNMP Trap ID
0
CIM Information
Prefix: PLAT ID: 0498
User Response
1. Make sure that the fans are operating, that there are no obstructions to the airflow (front and
rear of the server), that the air baffle is in place and correctly installed, and that the server cover
is installed and completely closed.
2. Check the ambient temperature. You must be operating within the specifications (see Server
Features and specifications for more information).
3. Check fan cable on rear HDD cable is connected correctly.
4. Check the fans on rear HDD cage are functional.
5. Replace rear HDD drive cage.
80010b01-0708ffff : Numeric sensor [NumericSensorElementName] going high (upper
non-recoverable) has asserted. (Rear BP2 Temp)
This message is for the use case when an implementation has detected an Upper Non-recoverable
sensor going high has asserted.
May also be shown as 80010b010708ffff or 0x80010b010708ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Temperature
SNMP Trap ID
0
CIM Information
Prefix: PLAT ID: 0498
User Response
1. Make sure that the fans are operating, that there are no obstructions to the airflow (front and
rear of the server), that the air baffle is in place and correctly installed, and that the server cover
is installed and completely closed.
2. Check the ambient temperature. You must be operating within the specifications (see Server
Features and specifications for more information).
3. Check fan cable on rear HDD cable is connected correctly.
Appendix A. Integrated management module II (IMM2) error messages
417

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents