Honeywell GX-Series Installation And Setup Manual page 81

Gx series;
Table of Contents

Advertisement

0 = Off
In this mode the panel will not automatically initiate a remote servicing call even if the panel
programming has changed. This is the default setting.
1 = Timed
In this mode, following modification to panel programming, a remote servicing call will be initiated
automatically between a programmed start time (option 47.4.2.1) and end time (option 47.4.2.2). To
avoid traffic congestion the panel selects a random time between the start and end times to initiate the
call. Once the connection is made, the new panel programming will be uploaded to the remote servicing
package.
2 = Instant
In this mode, following modification to panel programming, the connection to the remote servicing
package is initiated immediately, using call back number 1, on exiting engineering mode. Once the
connection is made, the new programming will be uploaded to the remote servicing package.
3 = Confirm
In this mode, when engineering mode is exited following a change to the panel programming, a message
is displayed at the keypad to asking whether a remote connection should be initiated. This must be
authorized by an appropriate user type before the call is made.
Once authorized, a two minute delay period is initiated. During this period, the engineer can initiate or
cancel the call.
If connection is initiated the panel uploads the new panel programming to the remote servicing package.
2 = Timers
This option selects the mode for automatic schedule to start a periodic upload. There are four further
options:
1 = Start Time
This is the start time of the off-peak window during which the panel can initiate an automated remote
servicing call. The default is 01:00.
2 = End time
This is the end time of the off-peak window of the automated remote servicing call. The default is 06:00.
3 = Sync Schedule
If this option is programmed, after a period equal to the number of days entered (0-365), the panel will
automatically carry out an automatic connection to the remote servicing application and upload the
latest panel programming during the off-peak window time programmed in menu 47.4.2.1=Start Time
and 47.4.2.2=End Time. The default number of days is 0 which disables the option.
4 = Schedule Reset
The schedule reset option controls the way in which the Sync Schedule operates. There are three
further options:
0 = Off
The panel will never initiate a remote servicing connection. This is the default setting.
1 = Auto Reset
This option resets the Sync Schedule timer after an automated connection.
2 = Manual Reset
This option resets the Sync Schedule timer after a copy of site data whether done automatically or
manually.
3 = Terminate Idle
This option allows a timeout period to be programmed into the panel which terminates a remote connection
after the programmed period of activity. This is programmable within the range 0-60 minutes. After
termination the panel records in the event log the message REM ABORT to indicate that the connection was
unexpectedly terminated. The default timeout period is 10 minutes.
GX-Series Control Panel Installation and Setup Guide
6-35