13 Security (Latch)
The Security output is activated whenever a Security zone is activated. The output is not subject the
Rearm parameter: it latches on and remains active until a valid code (type 2 or above) is entered.
14 AC Fail (Reflex)
The AC Fail output indicates the status of the AC (mains) power supply. The output activates when the AC
supply fails or an AC Fail zone is activated. The output is reset when the AC supply is restored or the AC
Fail zone is closed. The activation is delayed subject to the time entered in the 20=Power Delay parameter.
15 Battery Low (Reflex)
The Battery Low output activates whenever the control unit stand-by battery falls below 10.2V or a
Battery Low zone is activated. The output is restored when the voltage rises above 10.2V or the Battery
Low zone is closed.
16 Fire (Latch) {Not for UL installations}
The Fire output is activated whenever a Fire zone is activated. The output is not subject to the Rearm
parameter: it latches on and remains active until a valid code (type 2 or above) is entered.
17 Horn (Latch)
The Horn output is a general alarm output and is activated by most zone types in both the local and full
alarm modes. For example, a Fire zone activation causes the Horn output to pulse on and off – on for 0.5
seconds, off for 0.1 seconds. The Horn output is subject to the Bell Time, Bell Delay and No. Rearm
parameters.
18 E/E Horn (Latch)
The Entry/Exit Horn output has a dual function:
in an alarm condition its function is identical to that of the Horn output;
during the unsetting (disarming) and setting (arming) of the system it is used to provide an
indication on the status of the system. The indication states are as follows:
General Alarm - ON 500 msecs. OFF 500 msecs.
Clear to Exit - Continuous
Exit interrupted - ON 100 msecs. OFF 100 msecs.
75% Exit Time - ON 200 msecs. OFF 200 msecs.
Set - ON 600 msecs. OFF 600 msecs (twice)
Normal Entry - ON 800 msecs. OFF 200 msecs.
75% Entry Time - ON 200 msecs. OFF 200 msecs.
Fire - ON 500 msecs. OFF 100 msecs.
Chime - ON 500 msecs. OFF 400 msecs (twice)
19 Part Set (Reflex)
The Part Set output is activated when the assigned groups on the system are part set (part armed). This
output is a Reflex (follow) output and follows the part set and unset status of the groups.
20 Confirm (Latch)
The Confirm output is activated when there have been activations on two separate zones: the second
activation must occur within the Confirm Time Window. The zones do not have to be in the same group,
however, both groups must be assigned to the Confirm output to allow activation. Cross-group confirmation
is controlled by the Communications programming in menu 56.1, Int Telecoms or 56.5, Ext Telecoms.
If signaling is by DTMF format, cross-group confirmation will occur on groups that share the same confirm
channel. In all other signaling formats, cross-group confirmation will occur on groups that share the same
account number.
NOTE: The Confirm output is used to give positive identification that a genuine intruder alarm condition has
occurred and to minimize the possibility of false alarm activations.