Option 32 - Outputs - Honeywell GX-Series Installation And Setup Manual

Gx series;
Table of Contents

Advertisement

The response times of the zone circuits are reduced to 20 msecs for the duration of the Walk Test to
facilitate the detection of loose connections or damaged wiring. Once the Walk Test has started,
opening a zone (or a zone that is open at the start of the test) activates outputs programmed as
Entry/Exit Horn. If a single zone is open, the keypad displays the address and function of the zone.
If multiple zones are open, then the keypad indicates how many zones are open; the open zones can
be viewed by pressing the A> or <B keys.
NOTE: The Walk Test option does not display the status of the zones. If an open zone is included in the
Walk Test, the Entry/Exit Horn will activate as soon as the test is started and remains active
until the zone is closed.
While the Walk Test is active the message WALK TEST ACTIVE / ESC to abort is displayed;
press the # key to view all zones that have been walk tested so far. To return to the Walk Test press
the # key again.
2 = Audible
This option allows the user to do a Walk Test that does produce an audible sound. The Walk Test works
in the same way as the Silent Walk Test.
Ending the Walk Test
To terminate the Walk Test, press the esc key. The test will terminate automatically if no zones are
activated for 20 minutes.
The results of the test can be viewed by accessing the event log (refer to option 22 = DISPLAY LOG). The
start of the Walk Test is indicated by the display WALK TEST +; each zone that was tested is recorded (the
activation of each zone is recorded only once during the test — even if it was opened several times); the end
of the test is indicated by WALK TEST –.
Option 32 – Outputs
Outputs are tested by function: for example, when 01 = BELLS is selected, then all outputs programmed as
Bells are activated. Refer to option 53 = PROGRAM OUTPUT for a full description of each output
function.
On selecting the Outputs option, output function type 01 = BELLS is offered for selection. Press the A> or
<B keys to move to the required output function type. Alternatively, the function type number can be
entered directly, for example entering 13 selects SECURITY. To test the selected output function, press the
ent key. The ent key can be used to toggle the function ON and OFF as required. To exit from the Outputs
option, press the esc key.
Users
User types 2.5 & 3.6 only have access to 01 = BELLS and 02 = STROBE of the Output option. Only the
Engineer has access to all the output types.
GX-Series Control Panel Installation and Setup Guide
6-19