GX-Series Control Panel Installation and Setup Guide
Option 63 – Options
The Options function allows the GX-Series to be divided into group subsystems.
Options
63.1=Groups
On selecting Options, the keypad displays 1 = Groups; press the ent key to select this function.
1 = Group Mode
This option is used to enable the Groups function (default is 0 = Disabled). When enabled, the system
options that are eligible for group programming are then made available throughout the menu,
otherwise they do not appear.
Enabling Groups
On selecting 1 = Enabled, press the ent key to accept the programming and return to the previous
menu type.
NOTE: You must return to the Engineer Mode banner for groups to be fully enabled.
Disabling Groups
The Group Disabled feature operates as follows:
When disable groups is selected in menu option 63.1.1 two option are given:
1. Reset Groups
2. Disabled
If option 1 - Reset Groups is selected the engineer is prompted to confirm the selection. If confirmed, by
pressing the enter key, all group programming, for all the panel features, are reset to A1. When
engineering mode is exited a warning message is displayed (ATT!!! GRPS OFF, SYS.OP. IMPACT)
alerting the engineer that groups have been reset and there will be an impact on the operation of all
functions not programmed as group A1. This warning message will be displayed until the ESC key is
pressed by the engineer, acknowledging the warning.
NOTE: When group programming is re-enabled all previous group programming will not be restored.
If option 2 - Disabled is selected the engineer is prompted to confirm the selection. If confirmed, by
pressing the enter key, all group programming, other than A1 will be disabled (zones, outputs, links,
users). When engineering mode is exited a warning message is displayed (ATT!!! GRPSOFF, SYS. OP.
IMPACT) alerting the engineer that groups have been disabled and there will be an impact on the
operation of all areas not programmed as group A1. This warning message is displayed until the ESC
key is pressed by the engineer, acknowledging the warning.
NOTE: If this option is selected, when group mode is re-enabled all previous group programming will be
restored. However, while group mode is disabled, a zone not programmed to group A1 will not
operate normally on the system. It is strongly recommended that, whenever possible, groups are
always reset to A1 when disabling groups.
1 = Groups
1 = Group Mode
2 = Setting Logic
3 = Group Name
Figure 6-7. Options
0 = Disabled
1 = Enabled
A/B to move to group and ent to select.
Number keys to toggle:
- = status of group unimportant
S = Group must be set to allow group to set.
A/B to move to group and ent to select.
# = toggle upper case, lower case or library text.
* = delete last character.
A/B = move to character/word.
ent = assign character/word.
esc = save programming.