GX-Series Control Panel Installation and Setup Guide
46 = Resistance Select
RIOs, revision 1.2 and above, allow the zones to be programmed with different resistance preset values for
zone status activation. This feature allows selection of End Of Line or Double Balanced zone resistance
types. The on-board zones can also be modified using this feature.
The "EOL/Dbl. Bal." resistance types are selectable from this option. The system default value is 1k Fault
(Double Balanced). There are 10 preset pre-programmable resistance configurations:
1 = Preset 1 (BAL); 2 = Preset 1(EOL); 3 = Preset 2 (BAL); 4 = Preset 2 (EOL); 5 = Preset 3 (BAL);
6 = Preset 3 (EOL); 7 = Preset 4 (BAL); 8 = Preset 4 (EOL); 9 = 1K Fault (BAL); 10 = 1K Fault (EOL).
The tables that follow shows the resistance windows for each type:
NOTE: For UL 1076 installations, use 1K Ohm Single EOL configuration for all protective zones. Use EOL
resistor P/N 300-02343 supplied in SAP0166 package.
Option 01 - 1k
Tamper S/C
Low Res
800 – 900
Normal
900 – 1200
High Res
1200 – 1300
Open
1300 – 12000
Fault
Masked
12000 – 19000
Tamper O/C
19000 – infinity
Option 02 - 1k
Tamper S/C
Low Res
800 – 900
Normal
900 – 1200
High Res
1200 – 1300
Fault
Masked
1300 – 12000
Open
12000 – infinity
When a preset is selected, this will be the zone resistance range used by every zone on the system. Each zone
on the system can be further customized to a specific preset by using menu option 52.9, Resistance Select.
47 = Set Confirm
This parameter allows the system to emit a short double beep when the system/group has set (armed). There
are three options:
0 = Off
No indication.
1 = Alert on Set
A double beep when the system has set (armed).
2 = Alert on Comm {Required for UL installations}
A double beep after a successful signal to the ARC that setting (arming) has occurred.
48 = Alarm Limits
This parameter allows the user to program the maximum number of alarms, per group, which may be
transmitted to an Alarm Receiving Center in any set (armed) period. There are three options:
1 = No of Alarms
Option 03 – 2.2k
0 – 800
0 – 1800
1800 – 2000
2000 – 2500
2500 – 2700
2700 – 12000
-
-
12000 – 15000
15000 – infinity
Table 6-9. Preset value limits (ohms) - double balanced
Option 04 – 2.2k Option 06 – 4.7k Option 08 – 5.6k
0 – 800
0 – 1800
1800 – 2000
2000 – 2500
2500 – 2700
-
-
2700 – 12000
12000 – infinity
Table 6-10. Preset value limits (ohms) - end of line
Option 05 – 4.7k
Option 07 – 5.6k
0 – 3700
3700 – 4200
4200 – 5500
5500 – 6500
6500 – 19000
-
19000 – 22000
22000 – infinity
0 – 3700
3700 – 4200
4200 – 5500
5500 – 6500
-
6500 – 19000
19000 – infinity
19000 – infinity
6-48
Option 09 - 1k
Fault
0 -1400
0 - 800
1400 – 2800
800 - 900
2800 – 8400
900 -1200
8400 – 9800
1200 - 1300
9800 – 12600
1300 - 3500
-
3500 - 4500
12600 – 22000
4500 - 19000
22000 – infinity
19000 – infinity
Option 10 -1k
Fault
0 – 1400
0 - 800
1400 – 2800
800 - 900
2800 – 8400
900 - 1200
8400 – 9800
1200 - 1300
-
1300 - 4500
9800 – 19000
4500 - 19000
19000 – infinity