Honeywell GX-Series Installation And Setup Manual page 98

Gx series;
Table of Contents

Advertisement

GX-Series Control Panel Installation and Setup Guide
70 = SWDC Set Dly
When enabled, this parameter delays the indication of open zones at the start of a set (arm) sequence while
the Switch DC output (53.08) is active; this includes keypad text and sounders.
If there are no outputs programmed as Switch DC then there will be no delay at the start of the set (arming).
71 = MF BL Enable
When enabled, this parameter allows the panel to send a SIA event when the battery is low and there is a mains
power failure. When the event is sent, the Power Delay time set in parameter 51.20 stops immediately.
72 = Max Alm Cause
This option defines the range of valid cause codes, as agreed with the Alarm Receiving Center. When this
function is enabled, a cause code must be entered by the user when a reset of the system is required.
This parameter can be disabled by setting the alarm cause code to 000.
73 = Guard Unset
If set to 1 = Enabled this option allows a type 2.1 user code to unset (disarm) the system if an alarm has
occurred. The user code becomes type 2.4 after 3 minutes of the alarm but after 60 minutes returns to type
2.1. The user code can set (arm) the system at any time provided there are no outstanding resets required.
74 = Backup Link
If the Ethernet fails to report, this parameter, when enabled, allows the communication to revert to
Telecoms.
75 = Backup Timer
This is the time that the backup link is active. The time can be set from 0-300 seconds. The default is 90
seconds.
6-52