2=Bell Delay
This option is either enabled or disabled. When enabled, it will hold off the start of any bell delay time
programmed in parameter 03, until the end of the abort time programmed above.
04 = Exit Time
This parameter determines the time allowed to leave the premises via the exit route before the system sets
(arms). The Exit Time is programmable within the range 0–300 seconds; the default is 120 seconds.
Infinite Exit Time
Assigning a value of 000 seconds sets the Exit Time to infinity; an Exit terminator activation (Final or
Push-set zone) is required to complete the setting (arming) of the system. The infinite Exit Time is
normally used with a Push-set zone to terminate the setting (arming) and an Entry zone to start the
unsetting (disarming) procedure.
NOTE: If the system is programmed to Autoset and the Exit Time is programmed to 000, the Exit Time will be
set to 60 seconds for the Autoset — there is no requirement for a Push-Set zone to be activated.
Setting (Arming) Multiple Groups
This parameter can be assigned a different value for each group. If more than one is group is being set
(armed), the longest exit time is adopted for all setting (arming) groups.
05 = Entry Time
This parameter determines the entry time allowed to users when unsetting (disarming) the system. The
Entry Time is programmable within the range 0–300 seconds; the default is 45. Assigning a value of 000
seconds sets the Entry Time to infinity.
This parameter can be assigned a different value for each group.
NOTE: A Final zone assigned a * when programming the function will double the programmed Entry Time for the
group to which it is allocated.
06 = System Reset
This option allows the engineer or the remote code to determine the type that can reset the system following
an intruder alarm. The default type is 3.6 — manager; the programmable range is:
2.3–2.5 for the user
3.6 for the manager
3.7 for the engineer
This parameter can be assigned a different value for each group.
NOTE: This option is affected by reduced resets, menu option (51.55.3).
The panel only requests Engineer Level Reset if alarms have been signaled, via the Communication Module
and appropriate type reset is set to 3.7. If no signal is transmitted, the reset will automatically reduce to
type 3.6. This feature is only active when the DTMF signaling format is selected.
NOTE: This option can also be programmed from parameter 65 = Reset Levels.
07 = Tamper Reset
This option allows the engineer or the remote code to determine the code type that can reset the system
following a tamper. The default type is 3.7 — engineer; the programmable range is:
2.3–2.5 for the user
3.6 for the manager
3.7 for the engineer
This parameter can be assigned a different value for each group.
NOTE: This option is affected by reduced resets, menu option (51.55.3).