Use the A> or <B key to select the required group (A1–D8). When the end of a block is reached, the next
block of eight groups is displayed; use keys 1–8 to assign the relevant group in the current block to the zone;
press the ent key to accept the selection.
Account Group Autosetting
The GX-Series allows Account Group autosetting (autoarming). This means that several groups can be
bound together into one account group and, instead of a sending a normal CA event, the panel sends a CL
event.
Refer to menu option 56.1.2.2.2 = Communications.Internal Telecoms.Format.SIA.Group
Settings.Account No.
There are five stages to programming the Autoset function:
1. Autoset Status
0 = Off (default)
1 = On
2 = Monitor - if selected, the setting (arming) and unsetting (disarming) of the group is monitored:
if not set (armed) manually before the On time, then the Set Late output is activated
if unset (disarmed) before the Off time, then the Unset (disarmed) Early output is activated.
2. Prewarning
1 = Period
0 – 50 minutes (default 30 minutes):
2 = Audible (this can be turned ON or OFF)
This option determines the warning period given to users prior to the system autosetting. Outputs
programmed as Prewarning activate during the prewarning period. The output normally emits a
constant tone, however if an extension is not possible, then a pulsed tone is emitted and prewarn
activates at the Autoset time. At the end of the prewarning period, the system begins the timed setting
(arming) procedure.
NOTE: Pressing the esc key at any time during the prewarning resets and restarts the prewarning countdown.
If more than one group is in the prewarning period, each group can be viewed by pressing * and > or *
and <.
3. Extension
0 – 400 minutes (default 30 minutes):
An autoset Extension can be assigned to each group on the system - programmed with different values
per group. Entering a user code during the Prewarning delays the autosetting/arming by the period
assigned to the Extension.
NOTE: The Late Working option (refer to option 45 = TIMERS) authorizes an Extension in advance of the
Prewarning period.
Late Set appears if the system is not set (armed) after prewarn time plus 300 seconds (longest possible
exit delay) An Extension cannot be granted once the timed setting (arming) procedure begins.
4. Force Set
0 = Off (default)
1 = On
As a factory preset, any zone that is open at the start of the setting (arming) procedure - except Final,
Exit, Entry, or Push Set, (or Secure Final or Part Final when acting as a Final) - is omitted by the
autoset routine whether or not it is omittable. If one of the above listed zones is open and is non-
omittable, on expiry of the time programmed in the Fail-to-Set parameter the Fail-to-Set outputs are
activated along with a full alarm.
5. Weekly Schedule
This option assigns a programmed weekly schedule for each group when the selected group is automatically
switched On (Autoset) and Off (Autounset).
When the keyswitch is activated twice during the exit time of an autoset, the autoset is temporarily
cancelled for a few seconds, then it restarts the exit time causing the panel to reset.
GX-Series Control Panel Installation and Setup Guide