Canadian Option; Waterflow Silenceable; Mns Override; Auxiliary Power - Honeywell Notifier NFW-100X Manual

Addressable fire alarm control panel
Hide thumbs Also See for Notifier NFW-100X:
Table of Contents

Advertisement

Master Programming Level
While viewing the selected screen, press the number corresponding to the desired relay type to program the main circuit board relay. The
choice will be stored in memory and the display will return to the Relay Type Screen which will show the programmed type choice.
Press the Escape key to return to the Relays Selection Screen and repeat the preceding procedure for the remaining relays.
NOTE:
1. AR (AutoResettable) in SUPERVISORY AR and PROCMON AR means that a relay with the Supervisory and/or Process Monitor type
code, when activated, will automatically reset when the corresponding condition is cleared.
2. A relay programmed with the Silenceable Alarm type will activate upon any alarm and deactivate when the FACP Alarm Silenced LED is
illuminated.

Canadian Option

SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO

3=MNS OVERRIDE

System Setup Screen #3
Important! For Canadian Applications, this option must be set to ON prior to any other panel programming.
The Canadian Options configures the FACP with the following as required by Canada:
The following monitor module type codes are not available:
 monitor
 non-latching supervisory
 non-latching drill
 non-latching process monitor
 process monitor
 hazard
 tornado
 medical alert
The auto-silence timer is fixed at 20 minutes and cannot be changed.
Addressable ionization smoke detector sensitivity is automatically monitored using Canadian specifications.
The Positive Alarm Sequence and Pre-Signal option are not available for Canadian applications.
The F1 function key is automatically configured to perform a manual alarm signal activation when pressed.
The F2 function key is automatically configured to perform a two-stage bypass when pressed.
If NACs are set up for two-stage operation, the Silence Inhibit timer is automatically enabled and is fixed at 5 minutes.
AlarmNet supervision settings for Cellular and Ethernet communications are fixed at 3 minutes and cannot be changed regardless
of programming selection.

Waterflow Silenceable

SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
3=MNS OVERRIDE
System Setup Screen #3
MNS Override
SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
3=MNS OVERRIDE
System Setup Screen #3
MNS Override feature will become unavailable.

Auxiliary Power

SYSTEM SETUP
1=AUX POWER
2=TROUBLE REM
System Setup Screen #4
NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018
Pressing 1 while viewing System Setup Screen #3 will configure the FACP to comply with Canadian
requirements. The display will change to Canadian Opt. On. Each press of the 1 key will cause the display
to toggle between Canadian Opt. On and Canadian Opt. Off.:
NO
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
3=MNS OVERRIDE
Pressing 2 while viewing System Setup Screen #3 will allow the programmer to configure the system for
silenceable on nonsilenceable waterflow circuits. Each press of the 2 key will toggle the display between
Waterflow Sil. No and Waterflow Sil. Yes. When Waterflow Sil. No is selected, all output devices associated
NO
with a waterflow type input device, will be nonsilenceable. When Waterflow Sil. Yes is selected, all output
devices associated with a waterflow type input device, will be silenceable.
Pressing 3 while viewing System Setup Screen #3 will allow the programmer to configure the system for
use with the Mass Notification System (NFC-50/100 panel). Each press of the 3 key will toggle the display
between MNS Override No and MNS Override Yes. When MNS Override No is selected, the NFC-50/100
NO
panel does not have permission to override the FACP. When MNS Override Yes is selected, the NFC-50/100
panel will override the FACP, taking control of its NACs and control modules during a mass notification
event. Refer to the NFC-50/100 Manual for more information. When the Canadian Option is set to On, the
Two Special Application 24 VDC power outputs are available at TB11 on the main circuit board. Pressing 3
while viewing System Setup Screen #4 displays the following:
24HR
1=AUX 1
2=AUX 2
SYSTEM SETUP
NO
AUX POWER
Programming
79