Omron GRT1-CRT - 05-2008 Operation Manual page 62

Componet communications unit
Table of Contents

Advertisement

I/O Allocations to CompoNet Master Unit
Allocation Example
Input Area
Word
Bit 15
First
Status of CompoNet
word
Communications Unit
Not
+1
used.
+2
+3
These bits are not allocated
because the subsequent Unit is a
Word Unit.
Data Patterns in I/O Memory
• The system allocates 2 bits to each Bit Unit starting from the lower bits.
Bit Units are SmartSlice I/O Units that have two or more bits of I/O (for
example, the GRT1-ID4/OD4).
• The system allocates words to each Word Unit starting from words
with lower addresses. Word Units are SmartSlice I/O Units that have
one or more words of I/O (for example, the GRT1-AD2/DA2C).
Refer to the GRT1 Series SmartSlice I/O Units Operation Manual (Cat. No.
W455) for information on each Bit Unit and Word Unit model of SmartSlice
I/O Units and specifications.
3. Participation Status of the SmartSlice I/O Units
The system allocates 8 words for the participation status of the SmartSlice
I/O Units.
The system allocates words to the SmartSlice I/O Units in the sequence in
which they are connected (in the sequence of unit numbers). The models of
the SmartSlice I/O Units have no effect on the sequence of allocations.
Unless you use the CX-Integrator to set I/O allocations, the system always
allocates words in the same sequence starting from the first word for the node
address. The sequence is the status, left SmartSlice I/O Unit, subsequent
SmartSlice I/O Unit on the right side, other SmartSlice I/O Units. The system
allocates words to Input Units in the Input Area and to Output Units in the Out-
put Area.
The system allocates words for status of the CompoNet Communications Unit
and the participation status of the SmartSlice I/O Units in the Input Area.
Compo-
Unit 1
Net Com-
ID4
munica-
(4 bits)
tions Unit
8
Bit 0
#1
#2
#3
#4
You can make these patterns in I/O memory for I/O allocations.
Input Area
• Input data + Status of CompoNet Communications Unit (default setting)
• Input data + Status of CompoNet Communications Unit + Participation
status of SmartSlice I/O Units
Output Area
• Output data only
You can use the CX-Integrator to select from these patterns.
Slice I/O Units
Unit 2
Unit 3
Unit 4
Unit 5
Unit 6
ID4
ID4
AD2
OD4
ROS2
(4 bits)
(4 bits)
(2 words)
(4 bits)
(2 bits)
Section 5-3
Output Area
Word
Bit 15
8
Bit 0
Not
First
#6
#5
used.
word
43

Advertisement

Table of Contents
loading

This manual is also suitable for:

Smartslice grt1-crt

Table of Contents