Page 2
SmartSlice GRT1-CRT CompoNet Communications Unit Operation Manual Produced May 2008...
Page 4
Read and understand this manual fully before you use the CompoNet Communications Unit. After you read this manual, keep it in a safe location where it will be available for use when necessary. Be sure that the end user of the CompoNet Communications Unit has this manual.
Page 5
PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY. In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted. IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS...
Page 6
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses listed may be suitable for the products: •...
Page 7
PERFORMANCE DATA Performance data given in this manual is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual application requirements.
Page 8
Safety Precautions Safety Precautions Safety Indications The indications below are used in this manual for safety precautions which are necessary to use the CompoNet Communications Unit safely. The contents of these safety precautions are important. Al- ways obey them. These are the indications for safety precautions.
Page 9
Do not try to disassemble a Unit or touch the terminal block while the power is ON. Doing this can cause electrical shock. Make sure that the voltage and current input to the Units are in the specified ranges. If the voltage and current are not in the specified ranges, there can be Unit malfunctions or fire.
Page 10
GRAM mode. Fully make sure that it is safe before changing the status of bits or words in memory allocated to Output Slaves, Spe- cial I/O Units, or CPU Bus Units. If you change the bits or words al- located to a Slave or Unit, you could cause incorrect operation of the loads connected to the Slave or Unit.
Page 11
• Put a Unit in the special box during transportation. Make sure that the Unit is moved carefully, and not given too much vibration or shock during transportation. • Do not let a Unit fall or give it too much vibration or shock. This can cause malfunction or cause damage to the Unit.
Page 12
Precautions for Safe Usage • Be sure to turn OFF the power to the PLC and Slaves before doing these operations. • Assembling a SmartSlice I/O Terminal • Setting the rotary switches • Connecting cables • Be sure that there will be no bad effects on the system before doing these operations.
Page 13
Do not install the Units in these locations. • Locations with direct sunlight • Locations with temperatures or humidity not in the range specified in the specifications • Locations with condensation as the result of large changes in temperature • Locations with corrosive gases or flammable gases •...
Page 14
The 10-m regulations apply for radiated emissions. Low Voltage Directive Devices which operate at voltages from 50 to 1,000 VAC or 75 to 1,500 VDC must comply with the related safety requirements. The applicable standard is EN 61131-2. Complying with EC Directives The SmartSlice I/O Units comply with EC Directives.
Page 15
Related Manuals Related Manuals This table shows the manuals which are related to the CompoNet Communications Unit. Read these manuals together with this Manual. Cat. No. Manual Contents SmartSlice CompoNet This manual tells you about the functions, specifications, and W476 (this...
Page 16
Configuration CompoNet Communications Unit. Nomenclature and Section 2 tells you about the names and functions of the parts of the Section 2 Functions CompoNet Communications Unit. Section 3 tells you how to install the CompoNet Communications Section 3 Installing the Units Unit and SmartSlice I/O Units.
SmartSlice is a building-block style remote I/O system which you make from a Communications Unit and a number of SmartSlice I/O Units. Each SmartSlice I/O Unit has a small number of I/O points. You can use a SmartSlice I/O sys- tem to decrease wire connection, installation, and space requirements.
I/O capacity of each SmartSlice I/O Unit. After you complete registration, the CompoNet Communications Unit will compare the configuration with the table each time that the power is turned ON. You can set a status flag in the CompoNet Master Unit to show when the configurations do not agree.
Page 23
SmartSlice I/O Units. When you add the I/O Units, it will not be necessary for you to set the node addresses or I/O configurations. It will also not be necessary to change the ladder programming very much.
Section 1-3 System Configuration System Configuration This is an example of a CompoNet SmartSlice System. (7) CX-Integrator (1) CompoNet Master Unit Explicit message Remote I/O Communications CompoNet Slave I/O data (4) Right Turnback Unit GRT1-CRT ROS2 ROS2 UNIT PWR I/O PWR...
Page 25
You can normally connect a maximum of 64 SmartSlice I/O Units to one Com- poNet Communications Unit. There are restrictions in the number of Smart- Slice I/O Units if the total data size is too large or power supply capacity is too small.
Status area 1 word (This word shows the status of the CompoNet Commu- nications Unit.) Parameter backup You can back up or restore a maximum of 2 KB of data for one and restore CompoNet Communications Unit. Network power sup- 14 to 26.4 VDC...
Page 27
Flat Cable I (without sheath, DCA4-4F10) Flat Cable II (with sheath, DCA5-4F10) Note The Round Cable I, Round Cable II, Flat Cable I, and Flat Cable II are different types of cable. You must use a Repeater to divide a branch line from the main line to use more than one type of cable.
Nomenclature Section 2-1 Nomenclature This section tells you about the names and functions of the parts of the Com- poNet Communications Unit. 2-1-1 CompoNet Communications Unit GRT1-CRT UNIT PWR WORD I/O PWR NODE ADR ×10 ×1 [0-63] REGS BACK DC24V...
Section 2-1 Nomenclature 2-1-2 SmartSlice I/O Units A SmartSlice I/O Unit has three blocks. You can remove each block. Name Function Base Block This is the bus between the SmartSlice I/O Units. You do not have to disconnect the Base Block when you replace the Main Block, for example, when there is damage to the Main Block.
Indicators Section 2-2 Indicators This section tells you the specifications of the LED indicators on the front panel of the CompoNet Communications Unit. 2-2-1 MS Indicator The MS indicator shows the status of the CompoNet Communications Unit. UNIT PWR I/O PWR...
Section 2-2 Indicators 2-2-2 NS Indicator The NS indicator shows the communications status of the CompoNet net- work. UNIT PWR I/O PWR Color Status Green The Unit is online and the communications connection is completed. (The network status is normal.)
• The CompoNet Communications Unit could not make the Registration Table. • Pin 1 (REGS) of the DIP switch turned ON when pin 2 (I/O) was ON. You turn ON pin 1 to allocate I/O using software. You turn ON pin 2 to allocate I/O with the Reg- istration Table.
Indicators Section 2-2 2-2-4 UNIT PWR Indicator The UNIT PWR indicator shows the status of the Unit power supply. UNIT PWR I/O PWR Color Status Green The 24-VDC Unit power supply to the CompoNet Commu- nications Unit is ON. Not lit The Unit power supply is OFF.
Unit as a slave on the CompoNet network. Set the node address as a decimal number between 0 and 63. Set the 10s digit on the left rotary switch and set the 1s digit on the right rotary switch.
Page 38
Use pin 4 to back up the parameters of all installed SmartSlice I/O Units. If you turn pin 4 ON, OFF, ON in 3 s or less when pin 1 (REGS) or pin 2 (I/O) is ON, the parameters of all the SmartSlice I/O Units will be backed up to the CompoNet Communications Unit.
You can install the SmartSlice I/O Terminal in these directions. Installation Procedure 1,2,3... 1. Install the DIN Track. Use one screw for each three holes in the DIN Track. There must be a screw for each 105 mm or less. DIN Track One screw for each three holes...
(1) Press with force. Installation hook Note If the installation hooks do not lock correctly, release the hooks first, push the CompoNet Communications Unit against the DIN Track, and then lock the hooks. The subsequent page shows how to release the hooks.
You can normally connect a maximum of 64 SmartSlice I/O Units to one Com- poNet Communications Unit. (There are restrictions in the number of Smart- Slice I/O Units if the total data size is too large or power supply capacity is too small.)
Installing a SmartSlice I/O Terminal 3-1-4 Installing the End Unit You must install an End Unit (GRT1-END) to the end of the last block in the SmartSlice I/O Terminal. You connect it with the same procedure as for SmartSlice I/O Units.
Terminal. The End Plates prevent the blocks from moving. 1,2,3... 1. Put the bottom of the End Plate on the DIN Track. Then put the top of the End Plate on the DIN Track and pull down on the End Plate.
Right Turnback Unit Left Turnback Unit Slice I/O Unit Slice I/O Unit • You must install an End Unit (GRT1-END) on the end of the last block in the Precaution for SmartSlice I/O Terminal. Correct Usage • There are limits for each block to the capacity of the Unit power supply and the I/O power supply.
Page 47
Section 3-2 Installing the Turnback Units...
UNIT DC24V INPUT 2. Open the terminal cover on the Screw Terminal Block Adapter and connect the cable conductors to BDH (communications data high signal) and to BDL (communications data low signal) on the terminal block. For Round Cable II, also connect BS+ (communications power supply +) and BS −...
The power supply terminals on the CompoNet Communications Unit and Turnback Units are screwless clamp terminals. If you connect ferrules on the wires, all you must do to connect the wires is to push the ferrules into the ter- minals.
Page 51
H0.75/16 W 0.75 mm (AWG 18) H1.5/16 R 1.25 mm (AWG 16) Connecting Wires or Ferrules ■ Connecting Wires with Ferrules Push the ferrule fully into the wire hole of the screwless clamp terminal. Push the ferrule fully into the hole.
■ Connecting Wires without Ferrules Press in the release button adjacent to the connection hole of the screwless clamp terminal with a small flat-blade screwdriver. Then push the wire fully into the wire hole of the screwless clamp terminal and release the button.
4-2-5 Connecting the I/O Power Supply Cables Connect the I/O power supply cable (24 VDC) to the power supply terminals on the CompoNet Communications Unit. These terminals send 24-VDC power to the external I/O which connect to the SmartSlice I/O Units.
GRT1-TBL UNIT PWR I/O PWR UNIT DC24V INPUT Left Turnback Unit Turnback Cable Precaution for • The Turnback Cable does not send power. Connect the Left Turnback Unit to Correct Usage the same power supply as the CompoNet Communications Unit.
1. Refer to Appendix E Total I/O Current Consumption Table and calculate the total current consumption of all connected SmartSlice I/O Units. Include the Turnback Unit. 2. If the total current consumption is larger than 4 A, do one of these proce- dures:...
Page 56
Left Turnback Unit. Connect the I/O power supply (24 VDC) to the I/O power supply terminals on the Left Turnback Unit. • Add an I/O Power Feed Unit to start a new I/O power supply group. Make sure that each group uses less than 4 A.
Connecting the Signal Lines for External Devices Connecting the Signal Lines for External Devices Connect the I/O signal lines from the external devices to the I/O terminals on the SmartSlice I/O Units. The I/O terminals on the SmartSlice I/O Units are the same type of screwless clamp terminal as on the CompoNet Communica- tions Unit.
1. Turn OFF the Unit power supply to the CompoNet Master Unit and the CompoNet Communications Unit. 2. Set the 10s digit of the node address on the left rotary switch and set the 1s digit on the right rotary switch.
The SmartSlice I/O Unit on the right side of the CompoNet Communications Unit is Unit 1. The other SmartSlice I/O Units get unit numbers 2 to 64 in sequence from the left side to the right side of the SmartSlice I/O Terminal.
The system allocates words in an Input Area and Output Area to the Smart- Slice I/O Units using the node number of the SmartSlice I/O Terminal. These words are in the I/O memory of the CPU Unit of the CompoNet Master Unit. You can also use the CX-Integrator to set I/O allocations.
Page 62
The sequence is the status, left SmartSlice I/O Unit, subsequent SmartSlice I/O Unit on the right side, other SmartSlice I/O Units. The system allocates words to Input Units in the Input Area and to Output Units in the Out- put Area.
I/O Allocations to CompoNet Master Unit Section 5-3 Bits That Are Not The figure below shows a 4-bit Unit (Unit 5) that gets two bits in one word and Used two bits in the subsequent word. The subsequent Unit (Unit 6) is a Word Unit that gets two words.
Page 64
Unit Unit 7 Units Two-point Analog Input Unit (GRT1-AD2): 2 words (4 bytes) × 7 = 28 bytes in Input Area Two bytes are used for CompoNet Communications Unit status. The total is 30 bytes. • Word Output Units Only...
Unit Unit Unit Unit Unit 9 Units Two-point Analog Input Unit (GRT1-AD2): 2 words (4 bytes) × 9 = 38 bytes in Input Area Two bytes are used for CompoNet Communications Unit status. • Too Many Units 2-point 2-point 2-point...
Page 66
I/O Allocations to CompoNet Master Unit Section 5-3 Status of the This status word shows the status of the SmartSlice I/O Units in the Smart- CompoNet Slice I/O Terminal, the connection status with the CompoNet Master Unit, and other status.
Page 67
Participating Flags Withdrawn Flags * There is one Participating Flag and one Withdrawn Flag for each unit number (for each Slice I/O Unit). (There are flags for 64 Slice I/O Units.) The table below gives the meanings of the flags.
Page 68
The warning status in the CompoNet Communications Unit tells you the minor CompoNet errors that occur in the CompoNet Communications Unit. The warning status is not in an I/O area. You can access it only with an explicit message. Communications Unit This table shows the warning status.
Page 69
Section 5-3 I/O Allocations to CompoNet Master Unit Doing a Check of the Communications Status with the CX-Integrator You can use the CX-Integrator to do a check of the communications status. 1,2,3... 1. Start the CX-Integrator. 2. Right-click the icon of CompoNet Communications Unit and select Main- tenance Information.
The area is the mem- ory area in the CPU Unit and the address is the address of the first word to allocate. “Node” is the number of words in the Input or Output Area.
Page 71
SmartSlice I/O Terminal uses. To find the number of words in the Input and Output Areas, open the Configuration Window of the Communica- tions Unit and click the I/O Map Tab. The tab page will show the number of words in the Input Area and the Output Area.
The TS indicators must be lit in green. Correct Usage • Before making the Registration Table, make sure that pin 2 (I/O) on the DIP switch is OFF (Automatic I/O Allocation Mode). You cannot make the Registra-...
Section 6-2 Registration Table Turn ON pin 1 (REGS) on the DIP switch while the power to the SmartSlice I/O Terminal is ON. The CompoNet Communications Unit will read the I/O configuration informa- tion and make a Registration Table. The CompoNet Communications Unit will overwrite a previous Registration Table with the new one.
ON pin 1 to make the Registration Table again. tration Table. Note If you start with CompoNet Communications Unit with pin 1 ON and no Regis- tration Table, the TS indicator will flash in red. This shows a Registration Table Verification Error.
These conditions are necessary to back up the parameters. Do a check of these conditions before you back up the parameters. • Pin 1 (REGS) or pin 2 (I/O) on the DIP switch on the CompoNet Commu- nications Unit must be ON.
• There must be backup data in the CompoNet Communications Unit. • Pin 1 (REGS) or pin 2 (I/O) on the DIP switch on the CompoNet Commu- nications Unit must be ON.
The Automatic Restore Monitor Flag (bit 13 in the status word for the CompoNet Communications Unit) will also turn ON. If the new SmartSlice I/O Unit is not the same model as the previous Unit, the TS indicator on the CompoNet Communications Unit will flash in red.
SmartSlice I/O Terminal. The settings include the node numbers and I/O configurations. When you then add the SmartSlice I/O Units, it will not be necessary for you to set the unit numbers or I/O configurations. It will also not be necessary to change the ladder programming very much.
Page 80
First word +0 First word +1 You can set Dummy Units to make the I/O configuration information and lad- der programming for the maximum configuration. This will decrease the effects of changes in the SmartSlice I/O Unit configuration on the I/O configu-...
Table. Note (1) If pin 1 and pin 2 are ON when you turn ON the Unit power supply, the MS indicator will flash in red to show an error. The operation will stop. (2) If you turn ON pin 1 in Software I/O Allocation Mode, the TS indicator will come ON in red for 2 seconds to show an error.
2. Double-click the icon of the CompoNet Communications Unit. (In the Main- tenance Mode Window, right-click the icon and select Parameter − Edit.) The Configuration Window will show. 3. Click the I/O Module Tab and select the Use Software Configuration Mode Check Box. This will enable the Mount Check Boxes.
Page 83
Section 6-7 Software Setting of I/O Allocations 4. Select the Mount Check Boxes for all SmartSlice I/O Units in the Smart- Slice I/O Terminal and clear the Mount Check Boxes for all Dummy Units. Note By default, the Mount Check Boxes are selected for all SmartSlice I/O Units.
Page 84
Mode when the parameters are downloaded, the CX-Integrator will down- load only the normal parameters. (2) If you downloaded a Software Setting Table before, clear the Table, reset the power supply, and then download the Table from the CX-Integrator again.
Page 85
The CompoNet Communications Unit will clear the Software Setting Table. Note Clear the Software Setting Table and then set it again if you change the I/O size of any Slave (for example, changing the I/O size for the GRT1-AD2 or GRT1-TS2P).
4. Click the Close Button to complete the procedure. Note Click the I/O Map Tab from the Master Unit Configuration Window to show an I/O map of the Unit configuration that is set. You can also save the Unit config- uration in a CSV file.
Page 87
Section 6-7 Software Setting of I/O Allocations Saving the Unit Configuration in CSV Format 1,2,3... 1. Click the I/O Map Tab from the Master Unit Configuration Window and then click the Export Button. 2. Save the Unit configuration to a file.
Page 88
Section 6-7 Software Setting of I/O Allocations The CSV file will contain the Units that are set in the input and output areas and their I/O sizes.
Editing Parameters of SmartSlice I/O Units Installed Units Use this procedure to edit the parameters of installed Units. Installed Units are those for which the Mount Check Box is selected in the I/O Module Tab Page of the Configuration Window. 1. Start the CX-Integrator.
Unit Conduction Time Monitor Section 6-8 Note A Dummy Unit will return an error response if you send an explicit message directly to the Unit. The CX-Integrator is not required to do this. Unit Conduction Time Monitor The Unit Conduction Time Monitor records the total time that the internal cir- cuit power in CompoNet Communications Unit is ON.
2. Right-click the icon of CompoNet Communications Unit and select Main- tenance Information. (From the Maintenance Mode Window, double-click the icon.) The Monitor Window will show. You can monitor the Unit Conduction Time on the General Tab Page. 3. Click the Close Button to complete the procedure. 6-8-2 Setting the Threshold 1,2,3...
Section 6-9 Unit Comments 3. On the General Tab Page, enter a value for the Unit Conduction Time Threshold. The time can be between 0 and 429,496,729 hours. (The de- fault value is 0 hours.) 4. Click the Transfer [PC to Unit] Button to download the setting, and then click the Reset Button to reset the CompoNet Communications Unit.
The Monitor Window will show. The General Tab Page shows the comment. Note The comment shows by the icon of the CompoNet Communications Unit in the Maintenance Mode Window. 3. Click the Close Button to complete the procedure.
Network Communications Error History Monitor 3. On the General Tab Page, enter the comment in the Comment Field. 4. Click the Transfer [PC to Unit] Button to download the setting, and then click the Reset Button to reset the CompoNet Communications Unit.
CompoNet network Error in communications CompoNet Communications Unit The CompoNet Error 1 Communications Unit records previous errors in communications. Error 64 Refer to 9-2-3 Errors in SmartSlice I/O Terminals on page 102 for information on the contents of the error history.
Maintenance Information. (From the Maintenance Mode Window, dou- ble-click the icon.) The Monitor Window will show. 3. Click the I/O Unit Error History Tab. The window will show the last 64 er- rors in communications. You can click the Clear Button to clear the error history.
3. Click the OK Button to complete the procedure. 6-12-2 Writing the Last Maintenance Date 1,2,3... 1. Start the CX-Integrator. 2. Double-click the icon of the CompoNet Communications Unit. (In the Main- tenance Mode Window, right-click the icon and select Parameter − Edit.) The Configuration Window will show.
Page 98
Click the arrow buttons at the top of the calendar to show other months. Click the date at the bottom of the calendar to enter the date of today. 4. Click the Transfer [PC to Unit] Button to download the setting, and then click the Reset Button to reset the CompoNet Communications Unit.
Section 7-1 Setting Example and Basic Procedures Setting Example and Basic Procedures This section shows an easy example of the procedure for you to use a Com- poNet SmartSlice System. 7-1-1 System Setting Example This example shows a system which turns ON a lamp when you turn ON a switch.
This example tells you the most basic setting and application procedures. For information on other settings which are necessary for system operation, refer to the CS/CJ-series CompoNet Master Unit Operation Manual (Cat. No. W456) and the GRT1 Series SmartSlice I/O Units Operation Manual (Cat. No. W455).
SmartSlice I/O Units and be sure that the specifications are applicable. 7-2-1 Selecting the SmartSlice I/O Units You select the SmartSlice I/O Units for the numbers and types of I/O that are necessary. Refer to the datasheets and manuals for the SmartSlice I/O Units.
Section 7-3 Hardware Connections and Settings Hardware Connections and Settings This section tells you how to install, connect, and set a SmartSlice I/O Termi- nal. 7-3-1 Installing a SmartSlice I/O Terminal You install a SmartSlice I/O Terminal on DIN Track.
Page 105
Communications with all SmartSlice I/O Units will not start. If the TS indicator flashes in red, turn OFF pin 1, clear the Registration Table, reset the Unit power supply, and turn pin 1 ON again. The CompoNet Com- munications Unit will make a Registration Table for the configuration at the time.
Section 7-4 Starting Communications Starting Communications This section tells you how to make the I/O tables, start the system, and start communications. 7-4-1 Making the I/O Tables You must make I/O tables in the CPU Unit of the CompoNet Master Unit. The I/O tables show the Units in the PLC and their locations.
W456) for more information. 7-5-2 Doing a Check of I/O Use this procedure to see if the CPU Unit of the PLC correctly writes data to the Input Area and correctly sends data from the Output Area. 1,2,3... 1. Connect a PLC Programming Device (the CX-Programmer or a Program- ming Console) to the CPU Unit and enter the ladder program below.
8-1-1 I/O Response Time The I/O response time is from when an input at an Input Slave shows at the CompoNet Master Unit until it makes an output at an Output Slave. Both the Input Slave and Output Slave are in the SmartSlice I/O Terminal. The ladder program in the CPU Unit of the PLC processes the input to make the output.
Page 110
Refer to the SmartSlice GRT1 Series SmartSlice I/O Units Operation Manual (Cat. No. W455) for more information. Communications Cycle This is the time from communications with one SmartSlice I/O Unit until the Time of SmartSlice Bus: subsequent communications with the same SmartSlice I/O Unit.
Page 111
Section 8-1 Performance of Remote I/O Communications Note Refer to the CS/CJ-series CompoNet Master Unit Operation Manual (Cat. No. W456) for information on these variables: Communications cycle time of Com- poNet network (T ), interrupt processing time (T ), maximum/min-...
NetCyc Message Communications Time to the SmartSlice I/O Unit When you send a message to a SmartSlice I/O Unit, you must add the mes- sage communications time on the SmartSlice bus to the message communi- cations time to the CompoNet Communications Unit.
Page 113
Section 8-2 Performance of Message Communications...
Section 9-1 Error Procedures with Indicators Error Procedures with Indicators You can do a check for minor errors that occur with a SmartSlice I/O Terminal using the indicators on the CompoNet Communications Unit and SmartSlice I/O Units. This section tells you about the errors that the indicators show and the proce- dures for them.
Page 116
If the problem stays, replace the CompoNet Communica- tions Unit. Flashing Pin 1 (REGS) and pin 2 (I/O) Turn OFF one of these pins and reset the Unit power sup- on the DIP switch are ON. ply. The Registration Table data Make the registration table again.
Page 117
SmartSlice I/O Units • Make sure that there are no more than 64 SmartSlice I/O Units. • Make sure that the I/O size is no larger than 32 input bytes and 32 output bytes. Lit for 2 s Backup operation failure Back up the data again.
Make sure that there is a Unit power supply to the Left ply. Turnback Unit. I/O PWR Green Normal status Not lit There is no I/O power supply. Make sure that there is an I/O power supply to the Left Turnback Unit.
9-2-1 Communications Errors on CompoNet Networks You can use the Error History Tab Page in the CX-Integrator to see the last four communications errors between the CompoNet Master Unit and Compo- Net Communications Unit. The Error History Tab Page shows the error and the total Unit ON time when the error occurred.
The Status Tab Page of the CX-Integrator shows the communications status between the CompoNet Communications Unit and the SmartSlice I/O Units. Refer to 5-3-3 Status Words on page 46 for information on seeing the Status Tab Page. Status Tab Page...
You can see the last 64 communications errors between the CompoNet Com- munications Unit and SmartSlice I/O Units or internal errors in SmartSlice I/O Units. The error history gives an error description, the error code, and the total Unit ON time for errors in SmartSlice I/O Units.
Page 122
Kept Download the settings tion Table again. Cause 0x0B: Slave There is a checksum error parameters or invalid setting in one of these tables. 0x0C: Network parameters • Registration Table 0x0F: Backup/ • Slave parameters restore data • Network parameters •...
Page 123
Section 9-2 Error Procedures with CX-Integrator More Information on Errors in SmartSlice I/O Units Error code Error description “Detail” Keeping error Procedure (hexadecimal history during 1st byte 2nd byte value) power interruptions 0300 Reception error for backup 0x80: Node addresses Not kept •...
Make sure that the configura- tion of Repeater Units is correct. • Make sure that only one Slave uses the same I/O area words. If more than one Slave uses the same words, correct the node addresses. Set each node address on only one Slave.
Page 125
• If there are sources of noise in the area, do noise countermeasures for the Master Unit, Slaves, and communications cables. • If you are using an OMRON Master Unit and there is an error in the Master Unit, refer to the CS/CJ-series CompoNet Master Unit Opera- tion Manual (Cat.
Page 126
Possible cause and procedure The NS indicator on the CompoNet Communi- • If you are using an OMRON Master Unit, do a check of these items and cations Unit flashes green and comes ON in do the error procedure for the indicator status on the Master Unit.
Page 127
Section 9-3 Other Error Causes and Error Procedures...
The CMND instruction sends the FINS commands. You use the CX-Programmer to enter the CMND instruc- tion. When the CMND instruction sends a FINS command from the CPU Unit to the CompoNet Master Unit, the CompoNet Master Unit changes it into a CompoNet explicit message and sends it to the SmartSlice I/O Termi- nal.
Page 129
Service code (always 0094 hex) Destination node address The format below is for when the Unit cannot send the CompoNet explicit message or when there is a timeout. (FINS communications errors cause these problems.) 28 02 Command...
Page 130
The response will contain the response data defined for the service code. • Number of Response Bytes (Response) The response will contain the number of bytes of response data starting from the destination node address. • Destination Node Address (Response) The response will contain the node address of the SmartSlice I/O Terminal which sent the explicit response.
Page 131
0E hex 95 hex 01 hex C6 hex 2 bytes Read reads the alarm status bits for the CompoNet Communica- tions Unit. Note Refer to 5-3-3 Status Words on page 46 for information on status for the CompoNet Communications Unit.
Page 132
Read reads the alarm note.) information from the SmartSlice I/O Terminal. Note The table below shows the structure of the alarm information. 15 to 12 11 to 8 7 to 4 3 to 0 First word SmartSlice I/O Unit node...
Page 133
Class ID: 95 hex, Instance ID: 01 hex, and Attribute ID: 71 hex. The command code is 2802 hex (to send an explicit message). The command data is in words starting from D01000 in the CPU Unit. The words starting from D02000 will contain the response data.
Page 134
Example: Specify the word data 1234 hex in this sequence: 34 hex → 12 hex. Specify the double word data 12345678 hex in this sequence: 78 hex → 56 hex → 34 hex → 12 hex. These are the command formats.
Page 135
Starting with the Right Byte Starting with the Right Byte 08 07 08 07 (2) The sequence of data bytes is the same for service data in the response format. The right byte will be first for 2-byte or 4-byte data.
Contents Value Vendor code OMRON Cor- poration: ID = 47 (0x2F) Device type Communica- tions Adapter: ID = 12 (0x0C) Product code 1603 (0x0643) Revision Major = 01, Minor = 01 Status (bits supported) Serial number 00820A30 to 008390DF hex...
Page 137
80H: (Out slaves and Repeaters) Produced connection ID Consumed connection ID Initial comm.characteristics Produced connection size Consumed connection size Yes Expected packet rate Watchdog time-out action Produced connection path length Produced connection path Yes Consumed connection path length Consumed connection...
Appendix C Standard Models CompoNet Communications Unit Model Specifications GRT1-CRT SmartSlice CompoNet Communications Unit A total of 64 SmartSlice I/O Units can connect to one CompoNet Communica- tions Unit. SmartSlice I/O Units Model Specifications GRT1-ID4 Four-point SmartSlice DC Input Unit, NPN...
Page 139
GRT1-TS2T Two-point Temperature Input Unit Thermocouple input, Input type: R, S, K, J, T, E, B, N, L, U, W, or PL2 GRT1-CP1-L Positioning Unit with one counter (with encoder A, B, and Z Inputs), 1 digital input, and 2...
Appendix D Power Consumption and Weight Tables CompoNet Communications Unit Model Power consumption (W) Weight (g) GRT1-CRT SmartSlice I/O Units Model Power consumption (W) Weight (g) GRT1-ID4 GRT1-ID4-1 GRT1-OD4 GRT1-OD4-1 GRT1-ID8 GRT1-ID8-1 GRT1-OD8 GRT1-OD8-1 GRT1-ROS2 GRT1-AD2 GRT1-DA2C GRT1-DA2V GRT1-IA4-1 GRT1-IA4-2...
Page 141
Power Consumption and Weight Tables Appendix D...
Base Block Flat Cable baud rate Flat Cable Branch Line Connector automatic recognition Flat Connector Plug Bit Units I/O allocation calendar CX-Integrator communications cable software setting communications connector I/O configuration CompoNet Communications Unit Error Flag...
Page 145
NS indicator SmartSlice Bus Communications Error Flag SmartSlice configuration error SmartSlice I/O Terminals installation Output Area SmartSlice I/O Unit Alarm Flag SmartSlice I/O Unit Warning Flag SmartSlice I/O Units...
Page 146
Turnback Cable connecting Turnback Units installing unit comments reading writing Unit Conduction Time monitoring setting the threshold Unit Conduction Time Monitor threshold Unit Maintenance Flag unit numbers Unit power supply connecting terminals UNIT PWR indicator unused bits verification errors warning status...
Revision History A manual revision code shows as a suffix to the catalog number on the front cover of the manual. Page num- bers are those in the previous version. Cat. No. W476-E1-01 Revision code The following table outlines the changes made to the manual during each revision. Page numbers refer to the previous version.