CompoNet Explicit Messages
Command Operands
[ CMND S D C ]
S
D01000
D
D02000
C
D00000
Response
D02000
Note
(1) If the service data is two bytes or four bytes (for example, word data or error clear codes), specify
the right byte first in the command format.
Example: Specify the word data 1234 hex in this sequence: 34 hex → 12 hex.
Specify the double word data 12345678 hex in this sequence: 78 hex → 56 hex → 34 hex → 12 hex.
These are the command formats.
+0
: 2802 hex
+1
: 100B hex
+2
: 000E hex
+3
: 0095 hex
+4
: 0001 hex
+5
: 7100 hex
: First word for response data
+0
: 000B hex
+1
: 000E hex
+2
: 0000 hex
+3
: 0020 hex
:
+4
: 0000 hex
+5
: 0064 hex
+0
: 2802 hex
+1
: 0000 hex
+2
: 0008 hex
+3
: 100B hex
+4
: 008E hex
+5
: 2F07 hex
+6
: 0000 hex
Example for 1234 Hex
34
12
Service Data
Command code
Destination node address
(SmartSlice I/O Terminal: Node address 11)
Service Code 0E hex
Class ID 0095 hex
Instance ID 0001 hex
Attribute ID 71 hex
(The command does not use the rightmost two bytes (00)
because the number of data bytes is 11.)
Number of command data bytes: 11
Number of response data bytes: 14
Destination network address (CompoNet Master Unit): 0
Destination node address (CompoNet Master Unit): 0
Destination unit address (CompoNet Master Unit): 20 hex
Response necessary, communications port 0, number of
retries: 0 hex
Response monitor time
Destination node address: 11 (0B hex)
Normal end (8E hex)
The right byte goes in the higher bit addresses in memory for
the unit maintenance present value (0000072F hex). (Refer to
the note for more information.)
Example for 12345678 Hex
78
56
34
Service Data
Appendix A
12
115

Advertisement

Table of Contents
loading

This manual is also suitable for:

Smartslice grt1-crt

Table of Contents