Error Procedures with Indicators
Primary Errors That the Indicators Show and Error Procedures
Name
Color
Status
MS
Green
Lit
Red
Lit
Flashing
Not lit
NS
Green
Lit
Flashing
Red
Lit
Flashing
Not lit
Primary error
Normal status
Hardware fault in CompoNet
Communications Unit
Pin 1 (REGS) and pin 2 (I/O)
on the DIP switch are ON.
The Registration Table data
is corrupt.
The setting data for the
smart function is corrupt.
The backup data is corrupt.
There is no Unit power sup-
ply.
Normal status
The Unit is online but the
communications connection
is not completed. (The Com-
poNet Master Unit is com-
pleting the connection.)
The same node address is
set for two or more nodes on
the CompoNet network.
Communications stopped
because there are too many
communications errors.
Communications timeout
Node address duplication
check not complete
Error procedure
---
Reset the Unit power supply.
If the problem stays, replace the CompoNet Communica-
tions Unit.
Turn OFF one of these pins and reset the Unit power sup-
ply.
Make the registration table again.
Write the correct parameters again with the CX-Integrator.
Back up the data again.
Make sure that there is a Unit power supply.
---
• Make sure that you started the CompoNet Master Unit.
• Make sure that the SmartSlice I/O Terminal is in the
Registration Table in the CompoNet Master Unit.
Correct the node address settings and reset the Compo-
Net Communications Unit.
Do a check of these items and then reset the CompoNet
Communications Unit.
• Make sure that the trunk line cables and branch line
cables are not too long.
• Make sure that the cables are not broken or loose.
• Make sure that terminating resistance connections are
correct.
• Make sure that the CompoNet Units and cables are not
near sources of noise.
Do a check of these items and then reset the CompoNet
Communications Unit.
• Make sure that the trunk line cables and branch line
cables are not too long.
• Make sure that the cables are not broken or loose.
• Make sure that terminating resistance connections are
correct.
• Make sure that the CompoNet Units and cables are not
near sources of noise.
If only one CompoNet Communications Unit shows this
status, make sure that the connection of the communica-
tions cable is correct.