Ts Indicator - Omron GRT1-CRT - 05-2008 Operation Manual

Componet communications unit
Table of Contents

Advertisement

Indicators
2-2-3

TS Indicator

16
The TS indicator shows the status of the communications with the SmartSlice
I/O Units.
MS
UNIT PWR
NS
TS
I/O PWR
Color
Green
Lit
Flash-
ing each
second
Flashing
each 0.5
second
Red
Lit
Flashing
each 2
seconds
Flashing
---
Not lit
Status
The CompoNet Communications Unit is in communica-
tions with the SmartSlice I/O Units.
The SmartSlice I/O Units are joining communications at
this time.
• The CompoNet Communications Unit is backing up
parameters from the SmartSlice I/O Units.
• The CompoNet Communications Unit is restoring param-
eters to the SmartSlice I/O Units.
• Fatal communications error
• The CompoNet Communications Unit could not back up
the parameters from the SmartSlice I/O Units.
• The CompoNet Communications Unit could not restore
the parameters to the SmartSlice I/O Units.
• The CompoNet Communications Unit could not make the
Registration Table.
• Pin 1 (REGS) of the DIP switch turned ON when pin 2
(I/O) was ON. You turn ON pin 1 to allocate I/O using
software. You turn ON pin 2 to allocate I/O with the Reg-
istration Table.
Non-fatal communications error
• Communications timeout
• Registration Table verification error
• A replaced SmartSlice I/O Unit is the incorrect model.
• No power
• The CompoNet Communications Unit did not start com-
munications with the SmartSlice I/O Units.
• The CompoNet Communications Unit found an overcur-
rent.