Errors In Smartslice I/O Terminals - Omron GRT1-CRT - 05-2008 Operation Manual

Componet communications unit
Table of Contents

Advertisement

Error Procedures with CX-Integrator
9-2-3

Errors in SmartSlice I/O Terminals

Error History Tab
Page
More Information on Errors in the CompoNet Communications Unit
Error code
Error description
(hexadecimal
value)
0002
WDT error
0370
Verification error: Slave is
not there.
0372
Verification error: Slave is
participating but is not reg-
istered.
102
Indicator color
Red
The Alarm Status Bit for the SmartSlice I/O Unit is ON.
Yellow
The Warning Status Bit for the SmartSlice I/O Unit is ON
Blue
The SmartSlice I/O Unit has no errors.
You can see the last 64 communications errors between the CompoNet Com-
munications Unit and SmartSlice I/O Units or internal errors in SmartSlice I/O
Units. The error history gives an error description, the error code, and the total
Unit ON time for errors in SmartSlice I/O Units.
Refer to 6-11 I/O Communications Error History Monitor on page 76 for infor-
mation on seeing the Error History Tab Page.
"Detail"
1st byte
0x00
0x00
0x00
0x00
0x80:
Node addresses
SmartSlice
(hexadecimal
I/O
value)
Status
Keeping error
history during
2nd byte
power
interruptions
Kept
Not kept
Not kept
Section 9-2
Procedure
If this error occurs fre-
quently, replace the Com-
poNet Communications
Unit.
Connect the correct
SmartSlice I/O Units and
reset the CompoNet
Communications Unit.
Remove the SmartSlice
I/O Units that are not
necessary and reset the
CompoNet Communica-
tions Unit.