Omron GRT1-CRT - 05-2008 Operation Manual page 123

Componet communications unit
Table of Contents

Advertisement

Error Procedures with CX-Integrator
More Information on Errors in SmartSlice I/O Units
Error code
Error description
(hexadecimal
value)
0300
Reception error for backup
data
0374
Transmission error
Cause
A transmission error
occurred.
0375
Communications stopped
because of a transmission
error
Cause
A transmission error
occurred when the Unit
was set to stop communi-
cations for transmission
errors.
0376
Slave duplication error
Cause
A Slave duplication error
occurred.
0378
I/O size error
0379
SmartSlice configuration
error
104
"Detail"
1st byte
2nd byte
0x80:
Node addresses
SmartSlice
(hexadecimal
I/O
value)
0x80:
Node addresses
SmartSlice
(hexadecimal
I/O
value)
0x80:
Node addresses
SmartSlice
(hexadecimal
I/O
value)
0x80:
Node addresses
SmartSlice
(hexadecimal
I/O
value)
0x00
0x00
0x00
0x00
Keeping error
Procedure
history during
power
interruptions
Not kept
• Make sure that the
SmartSlice I/O Units are
correctly connected.
• Make sure that there
are no sources of noise
near the Unit.
Not kept
• Make sure that the
SmartSlice I/O Units are
correctly connected.
• Make sure that there
are no sources of noise
near the Unit.
Kept
• Make sure that the
SmartSlice I/O Units are
correctly connected.
• Make sure that there
are no sources of noise
near the Unit.
Not kept
Make sure that the
SmartSlice I/O Units are
connected correctly and
then reset the Compo-
Net Communications
Unit.
Not kept
Make sure that the
SmartSlice I/O Units are
connected correctly and
then reset the Compo-
Net Communications
Unit.
Not kept
Make sure that the
SmartSlice I/O Units are
connected correctly and
then reset the Compo-
Net Communications
Unit.