Connecting the Power Supply Cables
Applicable Wires for Screwless Clamp Terminals
Connecting Wires or Ferrules
32
■
Types and Sizes
Type
Stranded wires
AWG20 to AWG16 (0.5 to 1.25 mm
Solid wires
Ferrules
■
Stripping Length for Stranded Wires and Solid Wires
7 to 10 mm
■
Conductor Length for Ferrules
8 to 10 mm
We recommend the ferrules in the table below.
Manufacturer
Phoenix Contact AI0.5-10WH
AI0.75-10GY
AI1.5-10BK
Weidmüller
H0.5/16 OR
H0.75/16 W
H1.5/16 R
■
Connecting Wires with Ferrules
Push the ferrule fully into the wire hole of the screwless clamp terminal.
Push the ferrule fully into the hole.
Applicable wire gauge
Model
Applicable wire
2
0.5 mm
(AWG 20)
2
0.75 mm
(AWG 18)
2
1.25 mm
(AWG 16)
2
0.5 mm
(AWG 20)
2
0.75 mm
(AWG 18)
2
1.25 mm
(AWG 16)
Section 4-2
2
)
Crimping Tool
CRIMPFOX UD6 (order
number 1204436) or
CRIMPFOX ZA3 Series
PZ1.5 Crimping Tool (order
number 990599)