Omron GRT1-CRT - 05-2008 Operation Manual page 130

Componet communications unit
Table of Contents

Advertisement

CompoNet Explicit Messages
• Service Data (Command and Response)
In the command, specify the data defined for the service code.
The response will contain the response data defined for the service code.
• Number of Response Bytes (Response)
The response will contain the number of bytes of response data starting from the destination node
address.
• Destination Node Address (Response)
The response will contain the node address of the SmartSlice I/O Terminal which sent the explicit
response.
• Error Code (Response)
In an error response, the response will contain the error code defined by the CompoNet network.
Refer to Error Code Table, below, for more information.
Error Code Table
Response
Error name
code
08FF
Service not supported
09FF
Invalid attribute value
16FF
Object does not exist
15FF
Too much data
13FF
Not enough data
0CFF
Object state conflict
20FF
Invalid Parameter
0EFF
Attribute not settable
10FF
Device state conflict
14FF
Attribute not supported The attribute is not correct.
19FF
Store operation failure
• End Code (Response)
The response contains the end code for the FINS command.
Refer to the SYSMAC CS/CJ/CP Series and SYSMAC One NSJ Series Communications Command Reference
Manual (Cat. No. W342) for more information.
The service code is not correct.
The attribute value is not correct.
The write data is out of range
The instance ID is not correct.
The data is longer than the specified number of bytes.
The data is shorter than the specified number of bytes.
Command execution was not possible because of an internal hardware error.
A parameter is not correct.
The command specified a read-only attribute ID with a service code to write data.
Command execution was not possible because of an internal hardware error.
Saving data in memory was not possible.
Cause
Appendix A
111

Advertisement

Table of Contents
loading

This manual is also suitable for:

Smartslice grt1-crt

Table of Contents