If the warning A7AB Extension I/O configuration failure is shown,
•
make sure that the value of parameter 15.02 is CMOD-02.
•
set the parameter 15.01 value to CMOD-02.
You can now see the parameters of the extension module in parameter group
15 I/O extension module.
■
Diagnostics
Faults and warning messages
Warning A7AB Extension I/O configuration failure.
LEDs
The extension module has one diagnostic LED.
Color
Green
■
Technical data
Installation
Degree of protection
Ambient conditions
Package
Motor thermistor connection (60...61)
Maximum wire size
Supported standards
Triggering threshold
Recovery threshold
PTC terminal voltage
PTC terminal current
Short-circuit detec-
tion
The PTC input is reinforced/double insulated. If the motor part of the PTC sensor and wiring
are reinforced/double insulated, voltages on the PTC wiring are within SELV limits.
If the motor PTC circuit is not reinforced/double insulated (ie, it is basic insulated), it is
mandatory to use reinforced/double insulated wiring between the motor PTC and CMOD-
02 PTC terminal.
Relay output (62...63)
Maximum wire size
Optional I/O extension and adapter modules 457
Description
The extension module is powered up.
Into option slot 2 on the drive control unit
IP20 / UL Type 1
See the drive technical data.
Cardboard
1.5 mm 2
DIN 44081 and DIN 44082
3.6 kohm ±10%
1.6 kohm ±10%
≤ 5.0 V
< 1 mA
< 50 ohm ±10%
1.5 mm 2