Pollution degree
(IEC/EN 60664-1)
Atmospheric pressure
Vibration (IEC 60068-2)
Vibration (ISTA)
Shock/Drop (ISTA)
1) For symmetrically grounded TN-S systems, TT systems, and ungrounded or symmetrically
high-resistance grounded IT systems. See also section
high installation altitudes (page
2) For corner-grounded delta systems, midpoint-grounded delta systems and corner-grounded (via high
resistance) IT systems.
3)
IP66 (UL Type 4X) drive can be used outdoors if protected from the heat of the sun and indoors or
outdoors in a dusty environment.
Note: There are special considerations in corner-grounded installations above
2000 m. Contact your local ABB representative for further information.

Storage conditions

Store the drive in humidity controlled enclosed environments. Keep the drive in
its package.
Pollution degree 2
70...106 kPa
0.7...1.05 atmo-
spheres
Max. 1 mm (0.04 in)
(5...13.2 Hz), max.
7 m/s 2 (23 ft/s 2 )
(13.2...100 Hz) sinus-
oidal
-
Not allowed
125).
-
70...106 kPa
0.7...1.05 atmo-
spheres
-
R1...R4 (ISTA 1A): Displacement, 25 mm
peak to peak, 14200 vibratory impacts
R5...R9 ISTA 3E): Random, overall Grms
level of 0.52
R1...R4 (ISTA 1A): Drop, 6 faces, 3 edges
and 1 corner
Weight range
0...10 kg (0...22 lb)
10...19 kg (22...42 lb)
19...28 kg (42...62 lb)
28...41 kg (62...90 lb)
R5...R9 (ISTA 3E): Shock, incline impact:
1.1 m/s (3.61 ft/s)
Shock, rotational edge drop: 200 mm
(7.9 in)
Limiting relay output maximum voltages at
Technical data 351
-
60...106 kPa
0.6...1.05 atmo-
spheres
-
mm
in
760
29.9
610
24.0
460
18.1
340
13.4