Surrounding Air Temperature Derating, Ip55 (Ul Type 12) - ABB ACS580 Series Hardware Manual

General purpose drives
Hide thumbs Also See for ACS580 Series:
Table of Contents

Advertisement

280 Technical data
-099A-6, -125A-6, -144A-6: In the temperature range +40...45 °C (+104...113 °F), the
rated output current is not derated at all. In the temperature range +45...50 °C
(+113...122 °F), the rated output current is derated by 1% for every added 1 °C
(1.8 °F). The output current can be calculated by multiplying the current given in
the rating table by the derating factor (k):
k
1.00
0.95
0.90
0.85
0.80
0.75
...
-15 °C
+5 °F

Surrounding air temperature derating, IP55 (UL Type 12)

IP55 (UL Type 12) drive types, other than the exceptions below
In the temperature range +40...50 °C (+104...122 °F), the rated output current is
derated by 1% for every added 1 °C (1.8 °F). The output current can be calculated
by multiplying the current given in the rating table by the derating factor (k):
k
1.00
0.95
0.90
0.85
0.80
...
-15 °C
+5°F
IP55 (UL Type 12) drive type -077A-4, -078A-4, -260A-4, -293A-4; -075A-2 (R4), -273A-2,
-276A-2; -099A-6, -125A-6, -144A-6
-077A-4 and -078A-4; -075A-2 (R4): In the temperature range +40...45 °C
(+104...113 °F), the rated output current is derated by 1% for every added 1 °C
(1.8 °F). In the temperature range +45...50 °C (+113...122 °F), the rated output
current is derated by 2.5% for every added 1 °C (1.8 °F). The output current can be
+40 °C
+45 °C
+50 °C
+104 °F
+113 °F
+122 °F
+40 °C
+50 °C